INSTALLATION | Preparing to install the appliance
982000-AIR-M2-M4-EN03.1 | www.ochsner.com 19
Pipe diameter of the refrigerant line
Refrigerant line up to 6 m
Refrigerant line up to 8 m
Liquid line
Suction gas
line
Liquid line
Suction gas
line
AIR 7
10
18
10
18
AIR 11
12
18
12
18
AIR 18
12
22
12
22
AIR 23
12
22
16
2x22
AIR 29
16
2x22
16
2x22
AIR 41
16
42
16
42
AIR 41
16
4x22
16
4x22
Pipe diameter of the refrigerant line
Refrigerant line up to
10 m
Refrigerant line up to
12 m
Liquid line
Suction gas
line
Liquid line
Suction gas
line
AIR 7
10
18
10
18
AIR 11
12
22
12
22
AIR 18
12
22
12
2x18
AIR 23
16
2x22
16
2x22
AIR 29
16
2x22
16
2x22
AIR 41
16
42
16
42
AIR 41
16
4x22
16
4x22
Pipe diameter of the refrigerant line
Refrigerant line up to
14 m
Refrigerant line up to
16 m
Liquid line
Suction gas
line
Liquid line
Suction gas
line
AIR 7
10
18
10
18
AIR 11
12
22
12
22
AIR 18
12
2x18
12
2x22
AIR 23
16
2x22
16
2x22
AIR 29
16
2x22
16
35
AIR 29
16
2x22
16
3x22
AIR 41
16
42
16
42
AIR 41
16
4x22
16
4x22
Pipe diameter of the refrigerant line
Refrigerant line up to
18 m
Refrigerant line up to
20 m
Liquid line
Suction gas
line
Liquid line
Suction gas
line
AIR 7
10
18
10
18
AIR 11
12
22
12
22
AIR 18
12
2x22
12
2x22
AIR 23
16
2x22
16
2x22
AIR 29
16
35
16
35
AIR 29
16
3x22
16
3x22
9.4.3 Preparing the wall outlets
Whether the refrigerant lines between the indoor and
outdoor units are to be routed above or below ground, ap-
propriate and plant-specific wall outlets need to be created
through the outer wall of the building.
»
Ensure that the wall outlets are constructed in an ap-
propriate, plant-specific manner.
»
Take the construction of the wall (tiles, concrete) into
account.
»
Take the prevailing groundwater situation into
account.
Material damage
Incorrectly created wall outlets can cause signifi
-
cant damage to property, due to water (seepage,
condensation, floodwater) penetrating into the
building or stonework. Where the wall outlets are
created below ground level, the breach must be
appropriate to local conditions at the site (e.g.
non-accumulating or accumulating seepage water,
groundwater under pressure).
»
Use a suitable pipe liner or wall sleeve for the
wall outlet.
»
Tie the external end of the wall outlet in to the
external waterproof seal of the building.
»
Ensure that the pipe liner is arranged with a
slight fall (at least 2%) to the outside.
»
On both the outside and inside edge of the
wall, use appropriate ring seals to seal the
space between the wall sleeve and the re-
frigerant lines and electrical cables passing
through.
Material damage
PU foam is not suitable as a sealant for the pipe
liner.