Installation: 

 
Each installation must include the following components 

 

An isolating and non return valve must be fitted at the point of connection to the water supply. 

 

An anti leak device must be fitted at the point of connection to the water supply downstream 
of the isolating and non return valves. 

 

Pressure limiting devices should be installed to protect the cooler and feed pipework from 
water pressure surges in locations where they may occur 

 

Each cooler must have an independent isolating tap. This is intended so that the cooler can be 
replaced without draining long lengths of piping 

 
The following general guidelines apply to the pipework 

 

Pipework should avoid light fittings and electrical and gas piping 

 

Pipework in public view should be securely and neatly fixed. 

 

All pipework should be accessible and clearly labeled. 

 

Pipework should be lagged when necessary to avoid freezing or high temperatures. 

 
The customer should be informed in writing of the location of all isolation valves 
 

Sanitisation: 

 
EPDWA guidelines state: 

 

All coolers must be sanitized before commissioning 

 

When a customer signs up to the sanitisation program, the cooler should be sanitized every 6 
months 

 

Sanitisation should be carried out in accordance with the manufacturer’s instructions – see 
attached documents. 

 
Connecting Water Cooler to Mains Supply: 

 
All OASIS POU water coolers are supplied with a push-fit connector that should be used to connect the 
cooler to the mains water supply. OASIS recommends that these guidelines should be followed when 
installing the cooler: 
 
Use 

¼

” diameter tubing to connect the mains supply to the water cooler. Although 6mm tubing will 

appear to fit, it is actually approximately 5% smaller in size. The use of 6mm tubing will result in a leak. 
 
In any mains water system, it is possible for “spikes” or sudden fluctuations in pressure to occur. These 
can result in instantaneous pressures in excess of 7 bar (100 psig) to occur. OASIS recommend that all 
installations include a pressure regulator, such as a slow flow regulator, which should be located in front 
of the cooler’s water inlet.  

 
Installing the water cooler at your customer’s premises 

 
1.

 

Carry the cooler in the upright position to the customer’s premises  -  use the handle at the rear of 
the unit 

 

Summary of Contents for P1PVCDKY

Page 1: ...INSTALLATION SERVICE INSTRUCTIONS P1PVKY P1PVCDKY Contents...

Page 2: ...ion Cooler Installation General Troubleshooting Guidelines Cleaning and Sanitising Instructions Technical Specification Product Dimensions Height 1 110 mm Width 320 mm Depth 345 mm Net Weight 23 kg Fi...

Page 3: ...t Cold water temperatures may be adjusted via a slotted screw on the body of the control can be accessed through wires on the condenser Turning this screw in the clockwise direction will make the wate...

Page 4: ...g The entire internal water circuit and all the components which come in contact with water are food grade NSF WRAS approved Mounting Feet The unit is supplied with 4 mounting feet packed inside the f...

Page 5: ...n place e That the cooler is clean and dust free 5 Install your filtration system see relevant section in this manual 6 Flush out the water cooler a Connect the water supply to the bulkhead fitting at...

Page 6: ...g any shut off valve fitted to the installation or temporarily disconnecting the cooler from the mains Disconnect the cooler from the power supply Remove the top from the unit remove the two screws at...

Page 7: ...rward Remove the door from the cooler The inlet pipe is now visible on the left hand side of the filter compartment Installing the filter system It is recommended that you use a filter system with pus...

Page 8: ...e cooler in direct sunlight Do not locate the cooler next to a radiator Do not locate the cooler within or directly adjacent to toilet facilities Do not locate the cooler in constantly damp areas bene...

Page 9: ...l isolation valves Sanitisation EPDWA guidelines state All coolers must be sanitized before commissioning When a customer signs up to the sanitisation program the cooler should be sanitized every 6 mo...

Page 10: ...of installation g Level the machine using the adjustable feet 6 Connect the water cooler to a potable mains water supply OASIS recommend the use of an EPDA recognised installation kit that includes a...

Page 11: ...thermostat setting turn anti clockwise to increase the temperature setting of the cold water Disconnect the power from the unit and allow the the ice inside the cooler to melt Water dispensed from th...

Page 12: ...y Instructions Isolate the water cooler from the mains water supply this may be done by closing any shut off valve fitted to the installation or temporarily disconnecting the cooler from the mains Dis...

Page 13: ...0858 407 O RING 13 034507 002 COOLING TANK BASE 14 035023 001 DRAIN TUBE 3 8 ID 15 033970 003 DRAIN VALVE ASSY Equipment Household bleach 5 sodium hypochlorite Mild soap solution Plastic bucket One 12...

Page 14: ...ove the Filter Cleaning Cartridge Reconnect the blue tube to the tee piece or re install the filter system Reconnect the cooler to the mains water supply General Cabinetry Cleaning It is recommended t...

Reviews: