4  |  nVent.com

•  Apply a small amount of lubricant to the jacket 

surface near the end of the cable.

•  Avoid using large amounts of lubricant on the 

exposed end of the cable.

•  Insert prepared heating cable  

end into connector. Push until heating  

cable is fully inserted and end is visible  

through opening in connection cover plate.

Note: Heating cable cannot be removed.

 The connection 

and end seal are designed to be installed only once; the 

heating cable cannot be removed once installed.

5A

6

7

5B

•  Using wire cutters, cut away 1-inch of the braid.
•  Pull exposed braid back over metal clip.

•  Using wire cutters, cut away aluminum wrap.

•  Pull exposed braid back over metal clip.

IceStop and XL-Trace Only

HWAT Only

nVent RAYCHEM HWAT

nVent RAYCHEM IceStop and XL-Trace

•  Apply a small amount of lubricant to the jacket surface near 

the end of the cable.

•  Avoid using large amounts of lubricant on the exposed end 

of the cable.

• Insert prepared heating cable 

end into connector. Push until 

heating cable is fully inserted and 

end is visible through opening in 

connection cover plate.

Note: Heating cable cannot be removed.

 The connection 

and end seal are designed to be installed only once; the 

heating cable cannot be removed once installed.

Summary of Contents for Raychem RayClic Series

Page 1: ...instructions To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed and to comply with the requirements of nVent agency certifications...

Page 2: ...1 splice 2 warning E 1 Cable lubricant RAYCLIC T TEE KIT Item Qty Description A 1 Tee B 2 Plastic cable ties C 3 Clips D 1 End seal E 3 Labels 1 splice 2 warning F 1 Cable lubricant RAYCLIC X CROSS K...

Page 3: ...pipe and attach with plastic cable ties Score around and down the outer jacket of the heating cable 3 1 8 inches from the end Allow enough extra heating cable to make service loops as required Make su...

Page 4: ...cut away 1 inch of the braid Pull exposed braid back over metal clip Using wire cutters cut away aluminum wrap Pull exposed braid back over metal clip IceStop and XL Trace Only HWAT Only nVent RAYCHEM...

Page 5: ...e compressed Repeat steps 2 through 7 for all remaining heating cable entries Using glass cloth tape attach heating cable to pipe Apply insulation cladding warning labels and yellow splice identificat...

Page 6: ...steps 2 through 9 pages 3 5 Attach connector to mounting bracket by pressing until it snaps into place Complete heating cable installation and install drip loops as shown Protect heating cable from sh...

Page 7: ...Remove the outer jacket Do not cut or damage inner jacket Using wire cutters cut away aluminum wrap close to braid and outer jacket Remove exposed braid Push end seal completely onto heating cable No...

Page 8: ...ating cable does not have aluminum wrap Only HWAT heating cables have the aluminum wrap under the braid Skip the aluminum wrap removal step for XL Trace and IceStop heating cables Heating cable cannot...

Page 9: ...detail heating cable operation refer to the appropriate installation and operating manual Instructions 1 Open the RayClic Cover 2 Set multimeter to AC voltage function 3 Insert multimeter test probes...

Page 10: ...cations without notice Raychem IM H55388 RayClicConnectionKits EN 1805 PN 473303 000 nVent com North America Tel 1 800 545 6258 Fax 1 800 527 5703 thermal info nvent com Europe Middle East Africa Tel...

Reviews: