Tighten the 

screws until 

the metal top 

surface is at 

the same 

height as the 

inner clear 

plastic 

module.

®

R

8

10

11B

9

11A

11C

•  Securely tighten the two connection screws, alternating 

as they are being tightened.

•  Close the lid and snap the lever 

shut. Do not force lid closed. If lid does 

not close, check the connection to ensure 

all screws are fully tightened.

•  Tighten the nuts on the heating cable entries until 

grommets are compressed.

•  Repeat steps 2 through 7 for all 

remaining heating cable entries.

•  Using glass cloth tape,  

attach heating cable to pipe.

•  Apply insulation, cladding, warning  

labels and yellow splice identification label.

•  Using glass cloth tape,  

attach heating cable to pipe.

•  Apply insulation, cladding, warning  

labels and yellow splice identification label.

•  Using glass cloth tape,  

attach heating cable to pipe.

•  Apply insulation, cladding, warning  

labels and yellow splice identification label.

  WARNING: Fire hazard. Loose screws can cause 

excessive heating. Be sure screws are fully tightened.

SPLICE

TEE 

(insulation not shown)

CROSS 

(insulation not shown)

Summary of Contents for Raychem RayClic Series

Page 1: ...instructions To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed and to comply with the requirements of nVent agency certifications...

Page 2: ...1 splice 2 warning E 1 Cable lubricant RAYCLIC T TEE KIT Item Qty Description A 1 Tee B 2 Plastic cable ties C 3 Clips D 1 End seal E 3 Labels 1 splice 2 warning F 1 Cable lubricant RAYCLIC X CROSS K...

Page 3: ...pipe and attach with plastic cable ties Score around and down the outer jacket of the heating cable 3 1 8 inches from the end Allow enough extra heating cable to make service loops as required Make su...

Page 4: ...cut away 1 inch of the braid Pull exposed braid back over metal clip Using wire cutters cut away aluminum wrap Pull exposed braid back over metal clip IceStop and XL Trace Only HWAT Only nVent RAYCHEM...

Page 5: ...e compressed Repeat steps 2 through 7 for all remaining heating cable entries Using glass cloth tape attach heating cable to pipe Apply insulation cladding warning labels and yellow splice identificat...

Page 6: ...steps 2 through 9 pages 3 5 Attach connector to mounting bracket by pressing until it snaps into place Complete heating cable installation and install drip loops as shown Protect heating cable from sh...

Page 7: ...Remove the outer jacket Do not cut or damage inner jacket Using wire cutters cut away aluminum wrap close to braid and outer jacket Remove exposed braid Push end seal completely onto heating cable No...

Page 8: ...ating cable does not have aluminum wrap Only HWAT heating cables have the aluminum wrap under the braid Skip the aluminum wrap removal step for XL Trace and IceStop heating cables Heating cable cannot...

Page 9: ...detail heating cable operation refer to the appropriate installation and operating manual Instructions 1 Open the RayClic Cover 2 Set multimeter to AC voltage function 3 Insert multimeter test probes...

Page 10: ...cations without notice Raychem IM H55388 RayClicConnectionKits EN 1805 PN 473303 000 nVent com North America Tel 1 800 545 6258 Fax 1 800 527 5703 thermal info nvent com Europe Middle East Africa Tel...

Reviews: