Operating Manual and Inspection Book
POWER LIFT HL 2.30 NT / HL 2.35 NT / HL 2.40 NT
20100016 OPI
- 40 -
Version 1.1
8 Assembly and commissioning
Figure 20:
8.1 Set up guidelines
• Lift set up is done by trained manufacturer personnel or a contract partner. Set up is to be
done according to the assembly instructions.
• A standard lift may not be set up in explosion endangered spaces or wash halls.
• Before setting up, ensure or make a sufficient foundation.
• A level set up space is to be done in all cases, where open air and enclosed foundations
where frost is expected, must have a frost-depth thickness.
• An on-site standard electrical connection of 3 ~/N + PE, 400 V, 50 Hz is to be provided. The
supply is to be secured according to VDE0100 with 16 ampere fuses. The minimum line
cross-section is 2.5 mm².
• The lines can be fed through the cross-beams. In all cases, prevent kinks or tensional loads
on the lines.
• After successful lift installation and before first commissioning, the operating company must
have the lift grounding conductors inspected on-site according to IEC regulation (60364-6-
61). An insulation resistance test is also recommended.
8.1.1 Set up and anchoring the lift
On-site provision of suitable auxiliary materials (e.g. forklifts, crane, etc.)
are to be made available for unloading the lift and for assembly.
Before setting up the lift, the operating company must ensure or make a sufficient foundation. For
this, a normal reinforced concrete floor with a value of a min. C20/25 is required. The minimum
foundation thickness (without screed and tiles) is to be taken from the foundation plan in this
document.
In our plans, we inform of the minimum specifications for the foundation, however local conditions
(e.g. underground, floor quality, etc.) are outside of our responsibility. In special cases, the design
of the installation location must be individually specified by planning architects and statics
experts. Open air foundations must be made to frost depth.
The operating company of the lift is solely responsible for the set up location.
If the lift is to be assembled on an existing concrete floor, cement quality and strength are to be
checked beforehand. In case of doubt, make a test bore and insert an anchor. Then, tighten the
anchor to the manufacturer recommended torque. After inspection within the anchor zone of
influence (200 mm diameter) (see technical data sheet of the anchor manufacturer), if there is
visible damage
(hairline cracks, cracks or similar), or if the required torque cannot be applied then
the set up location is unsuitable.
Summary of Contents for HL 2.30 NT
Page 2: ......
Page 94: ...Notes ...