The divisor and rate multiplier are entered in the same manner as the divisor and
rate multiplier were entered in the
Liquid Measurement Using a Calculated Divisor
and Rate Multiplier
example.
Time Out Feature
The MC-II
Plus
Flow Analyzer has a Time Out Feature, which prevents it from being
left in the Calibrate Mode indefinitely. If the MC-II
Plus
Flow Analyzer is left in the
Calibrate Mode and no keypad activity is seen for approximately 10 minutes, it will
return to the Run Mode. If the unit is in Calibrate Mode and a Time Out occurs, any
data that has been input with the ENTER key being pressed afterward will be saved
to memory. Any data that has been input without the ENTER key being pressed
afterward will not be saved when Time Out occurs and the data entered from a
previous calibration will be retained.
Presetting Volume
Typically when a new flow analyzer is placed in service, the accumulated volume will
start at 0. In some applications where an existing piece of instrumentation is being
replaced, it is preferable to resume the volume where the former instrument left off.
The MC-II
Plus
Flow Analyzer has the capability to accept a preset volume. The
volume unit of measurement (BBL, GAL, etc) and the decimal position for the
volume (0.0, 0.00, etc.) must be defined prior to presetting the volume.
The steps required to preset a volume are:
1. Enter the calibration mode by pressing the
ACCESS
key.
2. At the prompt
tot Eng
, press
INCR
to select BBL, GAL, M³, MCF or USER.
Press
ENTER
.
3. At the prompt
tot d.P
, press
INCR
to change the decimal point position for the
volume. Press
ENTER
.
4. At
the prompt
SEt tot
, press
INCR
to toggle between
yES
or
no
until
yES
is
selected. Press
ENTER
.
5. At the prompt
SEt.tot
, use
INCR
and
STEP
to change the volume. The
currently selected volumetric unit of measure will be displayed and the current
decimal point will be indicated. Press
ENTER
.
6. At this point, the volume has been preset. Pressing
ACCESS
exits the
Calibrate Mode without making any further changes, or the remaining steps
may be implemented.
Summary of Contents for MC-II Plus Panel Mount
Page 44: ...MC II Plus WP PM Flow Analyzer Appendix A1 A1 10 May 2005 Flow Meter Input Wiring...
Page 46: ...MC II Plus WP PM Flow Analyzer Appendix A1 A1 12 May 2005 External Power Wiring...
Page 47: ...Appendix A1 MC II Plus WP PM Flow Analyzer May 2005 A1 13 4 4 to 20mA Rate Output Wiring...
Page 52: ...MC II Plus WP PM Flow Analyzer Appendix A1 A1 18 May 2005...
Page 62: ...MC II Plus WP PM Flow Analyzer Appendix A2 A2 10 May 2005...
Page 72: ...MC II Plus WP PM Flow Analyzer Appendix C C 8 May 2005 NOTES...
Page 78: ...MC II Plus WP PM Flow Analyzer Appendix D D 6 May 2005 NOTES...
Page 92: ......