LinMot Installation Guide
1 Important safety notes for E1200 series controllers
C A U T I O N !
In order to assure a safe and error free operation, and to avoid
severe damage to system components, all system components
must be directly attached to a single ground bus that is earth or
utility grounded (see chapter Power Supply and Grounding).
Each system component should be tied directly to the ground bus
(star pattern), rather than daisy chaining from component to
component. (LinMot motors are properly grounded through their
power cables when connected to LinMot controllers) (see chapter
Power Supply and Grounding).
All connectors must not be connected or disconnected while DC
voltage is present. Do not disconnect system components until all
LinMot controller LEDs have turned off. (Capacitors in the power
supply may not fully discharge for several minutes after input
voltage has been disconnected). Failure to observe these
precautions may result in severe damage to electronic
components in LinMot motors and/or controllers.
Do not switch Power Supply DC Voltage.
All power supply
switching and E-Stop breaks should be done to the AC supply
voltage of the power supply.
Do not connect or disconnect the motors from controllers
with
voltage present. Wait to connect or disconnect motors until all
LinMot controllers LEDs have turned off. (Capacitors may not fully
discharge for several minutes after power has been turned off).
Failure to observe these precautions may result in severe damage
to electronic components in LinMot motors and/or controllers.