Table 11
shows the diagnostic bits:
Register
Name
Description
Bit
HR_DIAGNOSE01
DIAG_RESTART_UNITS_ERROR
Units Configuration error.
0
DIAG_OUT1_OVERLOAD
Alarm output overload detection.
1
DIAG_ALM1_OUT_STATUS
Forced alarm state.
3
DIAG_ALM1_STATUS
Alarm status.
5
DIAG_FORCE_ALM1
Forced alarm function is enabled.
10
DIAG_FORCE_OUT1
Forced output function is enabled.
12
HR_DIAGNOSE02
DIAG_SENSOR_ERROR
Differential pressure sensor error.
0
HR_DIAGNOSE03
DIAG_OUT1_LIMIT_OOR
Input of retransmission limits outside the range.
1
DIAG_ALM1_SETPT_OOR
Input of alarm setpoints outside the range.
3
DIAG_FORCE_PRESS_OOR
Input of pressure forcing values out of range.
6
HR_DIAGNOSE04
DIAG_UNDER_RANGE
Indicates that the lower limit of the range has been
exceeded.
1
DIAG_OVER_RANGE
Indicates that the lower limit of the range has been
exceeded.
2
Table 11
– Diagnostic Bits