NOVUS AUTOMATION
16/28
NP785 Model: Configuration Registers Table
Address
Name
Description
R/W
Type
Standard
Min.
Max.
Decimal Places
100
HR_SENSOR_TYPE
Sensor type: 5 mbar or
20 mbar
RO
uint16
1
0
1
N.A.
101
HR_OUT1_TYPE
Retransmission output
type*
RW
uint16
0
0
1
N.A.
103
HR_OUT1_IN_HIGH_LIMIT
Retransmission upper
limit input
RW
int_32
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar:
3 decimal places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
104
HR_OUT1_IN_HIGH_LIMIT_H
105
HR_OUT1_IN_LOW_LIMIT
Retransmission lower
limit input
RW
int_32
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar:
3 decimal places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
106
HR_OUT1_IN_LOW_LIMIT_H
107
HR_OUT1_ERR
Error type (higher,
lower or low/high)*
RW
uint16
1
0
2
N.A.
108
HR_OUT1_HIGH_LIMIT
Retransmission upper
limit
RO
int_32
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar:
3 decimal places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
109
HR_OUT1_HIGH_LIMIT_H
110
HR_OUT1_LOW_LIMIT
Retransmission lower
limit
RO
int_32
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar:
3 decimal places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
111
HR_OUT1_LOW_LIMIT_H
113
HR_PRESS_FLTR
Filter for differential
pressure reading
RW
uint16
0
0
300
0
115
HR_UNIT_SYSTEM
Units configuration*
RW
uint16
0
0
4
N.A.
122
HR_A1FU
Alarm type*
RW
uint16
5
0
5
N.A.
123
HR_A1SPHI_IN
Alarm Setpoint High
Input
RW
int_32
0
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar:
3 decimal places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
124
HR_A1SPHI_IN_H
125
HR_A1SPLO_IN
Alarm Setpoint Low
Input
RW
int_32
0
-20 mbar
-290,08 mpsi
-8,029 inH2O
-203,94 mmH2O
-2000,0 Pa
20 mbar
290,08 mpsi
8,029 inH2O
203,94 mmH2O
2000,0 Pa
mbar:
3 decimal places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
126
HR_A1SPLO_IN _H
127
HR_A1BL
Alarm block
RW
uint16
0
0
1
N.A.
128
HR_A1HY
Alarm hysteresis
RW
uint16
0
0
4 mbar
58,02 mpsi
1,606 inH2O
40,78 mmH2O
400,0 Pa
mbar:
3 decimal places
mpsi:
2 decimal places
inH2O:
3 decimal
places
mmH2O:
2 decimal
places
Pa:
1 decimal place
129
HR_A1T1
Alarm time ON
RW
uint16
0
0
6500
0
130
HR_A1T2
Alarm time OFF
RW
uint16
0
0
6500
0
131
HR_A1IERR
Determines the alarm
status in case of
sensor error
RW
uint16
0
0
1
N.A.
132
HR_A1SPHI
Alarm Setpoint High
RO
int_32
0
-20 mbar
20 mbar
mbar:
3 decimal places