©Novinium, Inc. 2016, all rights reserved.
NRI 603 – Small Diameter Cables – SPR
Revised: February 19, 2016
Page
2
of
11
Installing Equipment
1.
Injection tool (IT).
Connect 12 to 18 inches of 1/8” tubing
to the Injection Tool (IT).
Connect a 1/8” x 1/8” ball valve for
typical injections.
Ultrinium 733 fluid can thicken severely
at temperatures below 50°F (10°C).
Using a 1/8” x ¼” ball valve may
improve injection times with long tube
lengths.
Figure 1:
Connect a ball valve
to the injection tool.
Install the liquid flow meter (rotometer).
Secure the liquid flow meter to the tank that is being used.
Figure 2:
Liquid flow meter.
Figure 3:
Flow meter secured on tank.
Connect the tank’s injection port (colored red) to the inlet of the flow meter.
Connect the tubing from the ball valve to the outlet of the flow meter.
Attach the injection tool to the IA, as in
NRI 452
.
Close all valves on the feed tank, flow meter, tubing, and gas tanks.
2.
Pressurized feed tanks.
Attach an inline pressure gauge to the CO2 regulator of the used gas tank.
Select an inline gauge with a pressure range appropriate for the injection.
Connect the inline gauge to the feed tank.
Wheel the CO2 regulator out to prevent accidental over-pressurization.
Flow meter
outlet
Flow
meter inlet
Filter