fixed. On special customer request for the algorithm “START-PAUSE-START” it’s possible to 
change the timing intervals and delays as per requirement

-

REV-201M has internally preprogrammed block that doesn’t allow to turn 

ON

 the power load on 

Channel 2

 until output contacts of 

Channel 1

 are being closed (

ON

).

2  GENERAL USE AND APPLICATION

2.1  FIRST START UP PREPARATIONS

2.1.1  

Safety precautions

All wiring or cable connections (disconnections) to the REV-201M must be necessarily made on fully 

deenergized device.

2.1.2

  All settings and adjustments of REV-201M should be made on deenergized device.

Adjustment should be made in the following sequence:

-

Setting the operation algorithm

-

Setting of timing parameters and delays

IMPORTANT NOTICES:

-

To change the operation algorithm of the REV-201M it’s necessary to turn OFF the power 
supply for the time of 0,5-1 seconds and change the position of the DIP switches “A” on the  
front panel (See Figure 1).

-

When changing the operation algorithm it’s necessary to take into account that newly set up  
algorithm will take effect only after full deenergization of the REV-201M input terminals with 
the subsequent turning ON of the device. 

-

If during operation any of the timing settings has been modified by the user it’s necessary 
to note that the new timing setting will take effect only from the next operation cycle (not 
immediately).

2.1.2.1

  Operation algorithms selection

List of the operation algorithms is shown in the Table 2 below. For more details kindly see paragraphs of 

section 1.2.3.

Select the required operation algorithm and set an appropriate position of DIP switches “

A

” (Fig.1).

Table 2

№ OPERATION MODE 

А

DESCRIPTION

1

Turn 

ON

 time delay

After   the   power   supply   application  REV-201M  performs   user 
preset time delay that will be followed by opening of the output 
contacts and REV-201M will switch to idle state. 

2

Impulse mode

After   power   supply   application   comes   time   delay   interval 
adjusted by the potentiometer knob 

T1

, then the output contacts 

close  for  the time  

T2

  and  by the end  of  the  

T2

  time  interval 

output contacts open and REV-201M comes to idle state

3

Cyclic mode

Periodic repetitive turning  

ON

/

OFF

  the output contacts with the 

preset timing intervals

4

Control operation mode

After power supply application REV-201M output contacts close, 
then   comes   fixed   time   interval   of   10   seconds   and   output 
contacts   open.   Then   comes   new   fixed   time   interval   of   30 
seconds   and   output   contacts   close   again   for   the   time   of   30 
seconds.   Then  contacts  open  and  REV-201M  switch  to  idle 
state.

NOTICE:

-

In case the DIP switches “

A

” position are set up in a different combination that is not stated in the 

table above – then LED indicators will flash with 

GREEN

 and 

RED

 color in turns and the output contact 

terminals will keep on being in open state.

-

When  using   the  REV-201M  in  

Control   operation  mode

  it   doesn’t   respond   to  any  position   or  

change of the knobs position 

D1

D2

 as well as timing knobs 

T1

T2

 (see Figure 1).

2.1.2.2  

Timing parameters adjustment.

REV-201М

     

                                                                                                                                                       

NOVATEK- ELECTRO

Summary of Contents for REV-201M

Page 1: ...NOVATEK ELECTRO LTD Research and Manufacture Company MULTIFUNCTIONAL TWO CHANNEL TIME DELAY RELAY REV 201 USERS MANUAL...

Page 2: ...ne case Mode 2 Parallel operation of the channels To each of two channels the power supply is applied simultaneously Thus the time countdown on each channel starts at the same time and comes one and t...

Page 3: ...201M 10 13 AC input terminals 240V for both Channels 11 12 DC input terminals 24V for both Channels 14 15 output terminals for both Channels 1 2 3 REV 201M operation algorithms Energized Turned ON sta...

Page 4: ...s determined as the sum of the values adjusted by both knobs for each channel separately When the power supply is present GREEN LED starts glowing and timing countdown begins After the expiry of time...

Page 5: ...n diagram ATTENTION For the proper operation of REV 201M it should be connected in accordance with the parallel channels operation Mode 2 for details kindly see paragraph 1 1 Application After the pow...

Page 6: ...tion List of the operation algorithms is shown in the Table 2 below For more details kindly see paragraphs of section 1 2 3 Select the required operation algorithm and set an appropriate position of D...

Page 7: ...hanged as per requirement 2 1 3 Connect REV 201M as shown on Figure 7 depending on the chosen operation mode Paragraph 1 1 Figure 7 Wiring diagram depending on required operation mode ATTENTION It is...

Page 8: ...nufacturer guarantees safe operation of the device within 36 calendar months from the sales date on the following conditions Proper device connection according to the points stated in this present man...

Page 9: ...8225029 H5S YB4 X H3CR A 301 AC100 240 DC100 125 H3CR AS AC24 48 DC12 48 H3DK GE AC240 440 H3RN 2 AC24 H3RN 21 AC24 H3CR H8RL AC DC24 M H3CR H8RL AC100 120 S H3CR G8EL 31 AC100 120 H3CR H8RL AC100 120...

Reviews: