This present manual contains necessary information about application, main operation principles and 

adjustment setting for the two-channel electronic time delay relay REV-201M (hereinafter 

REV-201М

).

1  GENERAL DESCRIPTION AND OPERATION

1.1  APPLICATION

REV-201M is designed for the commutation of electrical circuits of 240V 50Hz AC as well as 24 – 100V DC 

electrical circuits with the adjustable time delay setting. 

REV-201M contains 2 channels – each of them may work in 4 user preset algorithms:

-

Turn ON

 time delay relay;

-

Impulse relay;

-

Cyclic relay for the periodic events;

-

Operation relay *. 

_________

* REV-201M could be used as the relay of pre-starting signalization for the machinery that require to  

announce that some mechanism or machinery will soon take a start to make people aware of this and get  
away   from   the   risky   zones.   Widely   used   for   steel   plants,   heavy   machinery,   cranes   and   construction 
mechanisms as well as mining companies for the technological stuff safety.

Time   delay   setting   for   each   channel   starts   from   the   moment   of   the   power   supply   given   to   the 

corresponding channel. REV-201M allows to provide 2 modes of operation:

Mode   1.  Independent  operation  of  channels.

  To   each   of   two   channels   power   supply   is   given 

independently and thus each channel starts the countdown from the moment the power supply is given. This is 
the mode when 2 independent time relays are functioning in one compact case housing (2 time delay relays in 
one case).

Mode  2.  Parallel   operation  of   the  channels.

 

To  each  of   two   channels   the   power   supply  is   applied 

simultaneously. Thus the time countdown on each channel starts at the same time and comes one and the 
same input power supply. Triggering time corresponds to the user-adjusted settings for each of the channels. 
So the REV-201M in this mode operates like one time delay relay with 2 output contacts that have the same or 
different time settings.

ATTENTION!!!   When  using  the  REV-201M  in  Mode  1.  The power supply of both channels must 

necessarily have common neutral.

1.2  TECHNICAL PARAMETERS

1.2.1

 Basic technical characteristics are shown below in Table 1.

Table 1

Rated AC input power supply (terminals L, N), V

160 – 300

Rated DC input power supply (terminals  +24, N), V

24 10%

Rated power circuit frequency, Hz

50 – 60

Initialization readiness time after the power supply application to the channel, 
sec, less then

0,25

Timing accuracy, %, not less then

1,5

Time setting accuracy (scale accuracy), %, not less then

3

Number of operation algorithms

4

User -adjustable time range, sec

0 – 36000

Time setting adjustment

Smooth

Number of scale marks for the potentiometer knobs

10

Type and quantity of the output commutation terminals

1 changeover

Protection degree:                     -  housing

                          - contact terminals

ІР40
ІР20

Commutation lifetime of the output terminals at cos=1:
                                        - under the load of 7А, times, not less then 
                                        - under the load of 1А, times, not less then

100 000
1 000 000

Rated power consumption (under the load), VA, not more then

1,0

Weight, kg, not more then

0,150

Outer dimensions, mm

35 х 92 х 58

Operation temperature range, °С

From - 20 to +55

Storage temperature, °С

From - 45 to +70

REV-201М

     

                                                                                                                                                       

NOVATEK- ELECTRO

Summary of Contents for REV-201M

Page 1: ...NOVATEK ELECTRO LTD Research and Manufacture Company MULTIFUNCTIONAL TWO CHANNEL TIME DELAY RELAY REV 201 USERS MANUAL...

Page 2: ...ne case Mode 2 Parallel operation of the channels To each of two channels the power supply is applied simultaneously Thus the time countdown on each channel starts at the same time and comes one and t...

Page 3: ...201M 10 13 AC input terminals 240V for both Channels 11 12 DC input terminals 24V for both Channels 14 15 output terminals for both Channels 1 2 3 REV 201M operation algorithms Energized Turned ON sta...

Page 4: ...s determined as the sum of the values adjusted by both knobs for each channel separately When the power supply is present GREEN LED starts glowing and timing countdown begins After the expiry of time...

Page 5: ...n diagram ATTENTION For the proper operation of REV 201M it should be connected in accordance with the parallel channels operation Mode 2 for details kindly see paragraph 1 1 Application After the pow...

Page 6: ...tion List of the operation algorithms is shown in the Table 2 below For more details kindly see paragraphs of section 1 2 3 Select the required operation algorithm and set an appropriate position of D...

Page 7: ...hanged as per requirement 2 1 3 Connect REV 201M as shown on Figure 7 depending on the chosen operation mode Paragraph 1 1 Figure 7 Wiring diagram depending on required operation mode ATTENTION It is...

Page 8: ...nufacturer guarantees safe operation of the device within 36 calendar months from the sales date on the following conditions Proper device connection according to the points stated in this present man...

Page 9: ...8225029 H5S YB4 X H3CR A 301 AC100 240 DC100 125 H3CR AS AC24 48 DC12 48 H3DK GE AC240 440 H3RN 2 AC24 H3RN 21 AC24 H3CR H8RL AC DC24 M H3CR H8RL AC100 120 S H3CR G8EL 31 AC100 120 H3CR H8RL AC100 120...

Reviews: