~ 5 ~
NOVATEK-ELECTRO MCK-108
Table 1
- General Data
Name
Value
Purpose of device
Control and distribution equipment
Rated operating regime
continuous
Protection class
IP20
Electric shock protection class
II
Climatic version
N
С 3.1
Allowable pollution rating
II
Overvoltage category
II
Rated insulation overvoltage, V
450
Rated impulse withstand voltage, kV
2.5
Connecting terminals wire section, mm
2
0.5
– 2
Tightening torque of terminal screws, N*m
0.4
Table 2
- The main technical characteristics
Name
Value
Rated supply voltage: single-phase 50 Hz, V
230/240
Voltage, at which operability is maintained:
- minimum, V
- maximum, V
130
265
Mains frequency, Hz
48
– 62
Analog Inputs:
- input for connecting level sensor (of pressure)
- general for level sensors (of pressure)
4
1
Main outputs:
- pump relay - make contact for controlling electric motor starter - 10 A 250 V at cos
φ=1, piece
- functional relay
– transfer contact - 10 A 250 V at cos φ=1,
piece
1
1
Controlled environment resistance for conduction-measuring sensor, kiloohm, not
more than
450
Power consumption (under pressure), not more than, W
3.3
Weight, not more than, kg
0.2
Overall dimensions, mm
Figure 1
Installation onto standard 35 mm DIN rail
The device preserves functionality in any position within the space
Casing material
– self-extinguishing plastic
Table 3
- The characteristics of the integrated relays output contacts
Operating
regime
Max. current at
U~250
V, A
Number of trips
х1000
Max. switching
power, VA
Max. current at
Uconst.=30 V, A
cos
= 0.4
cos
= 1.0
5
10
50
100
4000
3
3 INTENDED USE
3.1
Preparation for operation
3.1.1 Preparation for connection:
–
Unpack the product (we recommend to keep the original packing for the entire warranty period of the product
operation);
– Check the product for damage after transportation; in case of such damages detection, contact the supplier
or manufacturer;
–
Carefully study the Operating Manual (
pay special attention to the connection diagram to power the
product
);
–
If you have any questions regarding the installation of the product, please contact the manufacturer by
telephone number indicated at the end of this Operating Manual.
3.1.2 General instructions
ATTENTION! MCK-108 ARE NOT DESIGNED FOR LOAD COMMUTATION IN CASE OF SHORT CIRCUITS.
THEREFORE THEY SHOULD BE PROTECTED BY AUTOMATIC CIRCUIT BREAKERS (FUSES) WITH
TRIPPING CURRENT NOT EXCEEDING 10 A.
ATTENTION! ALL CONNECTIONS MUST BE PERFORMED WHEN THE DEVICE IS DE-ENERGIZED.
Error when performing the installation works may damage the product and connected devices.