In the automated 

drainage mode

, if the emergency level has been reached, the electric motors of the pumps 

are activated simultaneously. 

 

3.2.3 Emergency conditions 

3.2.3.1 Protection of the pump electric motor from the inadmissibly low liquid level in the well 

Protection works if the 

DR

 sensor is activated. 

If the liquid level in the well falls lower than the 

DR

 sensor: 

- the pump electric motor is deactivated; 
- the LED 

DR

 starts to glow red; 

- the functional relay activates the alarm (at operation with one electric motor). 
If the liquid level reaches the 

DR

 sensor and the AR time elapses, the pump electric motor will be activated. 

If the 

DR

 sensor is off, the LED 

DR

 goes out. 

 

3.2.3.2 Emergency shutdown of the pump electric motor on tripping of the 

EL

 emergency level sensor. 

 If the 

EL

 sensor is activated, on the liquid level reaching the 

EL

 sensor: 

-  in  the  automated 

filling  mode

  the  work  of  the  pump  electric  motor  is  forbidden  (when  working  with  two 

pumps the work of both pumps electric motors is forbidden); 

-  in  the  automated 

drainage

  mode  the  pump  electric  motor  is  activated  (when  working  with  two  pumps  the 

work of both pumps electric motors is allowed) ; 

- the LED 

EL

 starts to glow red; 

- when working with one pump electric motor, the functional relay activates the alarm. 
If the liquid level falls lower than the 

EL

 sensor: 

- the pump electric motor is activated (when working with two pumps the work of both pumps electric motors is 

allowed); 

- the LED 

EL

 goes out; 

- the functional relay deactivates the alarm. 
If the 

EL

 sensor is off, the LED 

EL

 goes out. 

 

3.2.3.3

 

Failures of the (pressure) level sensors are specified in Table 4 

 

Table 4             

 

Name of Failure 

Cause 

Indication 

Failure  of  the  lower  level 
sensor (

LL

If  the 

UL

  or 

EL

  sensor  has  tripped  (except  for 

the  operation  mode  with  the  pressure  sensor), 
the 

LL

  sensor  shall  indicate  the  absence  of 

liquid. 
Or  if  the 

UL

  or 

EL

  sensor  has  tripped  (in  the 

operation  mode  with  the  pressure  sensor),  the 

LL

 sensor shall indicate a closed condition. 

The LED 

LL

 blinks red 

Failure  of  the  upper  level 
sensor (

UL

If  the 

EL

  sensor  has  tripped,  the 

UL

  sensor 

shall indicate the absence of liquid. 

The LED 

UL

 blinks red 

 

At  failure  of  the 

UL

  sensor,  MCK-108  will  continue  operating,  using  the  emergency  level  sensor  as  an 

UL

 

sensor. 

 

3.2.3.4 EEPROM Failure 
When EEPROM failure, calibration of resistance of liquid off and MCK-108 is locked, giving the following error 

message 

– in turn and with 1 Hz frequency 

EL

UL

LL

DR

 LEDs starts to glow

 

and upside-down. Then the cycle is 

repeated. 

 

ATTENTION! 

In case of EEPROM failure

 

the MCK-108  needs to be laid off and sent for repair. 

 

3 MAINTENANCE 

3.1

 

SAFETY PRECAUTIONS

 

 

THE  TERMINALS  AND  THE  PRODUCT  INTERNAL  ELEMENTS  CONTAINS  POTENTIALLY  LETHAL 
VOLTAGE. 
DURING  MAINTENANCE  IT  IS  NECESSARY  TO  DISABLE  THE  PRODUCT  AND  CONNECTED 

              DEVICES FROM THE MAINS. 

3.2

 

Maintenance of the product must be performed by qualified service personnel. 

3.3. Recommended frequency of maintenance is 

every six months.

 

 

3.4.

 

MAINTENANCE PROCEDURE

1) Check the connection reliability of the wires, if necessary, clamp with the force specified in Table 1; 

Summary of Contents for MCK-108

Page 1: ...pment and production complies with requirements ISO 9001 2015 Dear customer Company NOVATEK ELECTRO LTD thanks you for purchasing our products You will be able to use properly the product after carefu...

Page 2: ...UT DISCONNECTING THE PRODUCT FROM THE MAINS TO OPEN AND REPAIR THE PRODUCT INDEPENDENTLY TO OPERATE THE PRODUCT WITH MECHANICAL DAMAGES OF THE CASE IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND...

Page 3: ...g the tear and wear the user can set the alternate operation of the pumps To prevent failure of the electric motor while draining the well one may use a dry run sensor conduction measuring dry run sen...

Page 4: ...lling mode it glows red while in the drainage mode it blinks green 13 LED UL Upper Level glows red if the liquid level is higher than the upper level sensor 14 LED EL Emergency Level glows red if the...

Page 5: ...o standard 35 mm DIN rail The device preserves functionality in any position within the space Casing material self extinguishing plastic Table 3 The characteristics of the integrated relays output con...

Page 6: ...ure of the terminal block screws or the compression of the connected wire To increase the running ability of MCK 108 it is recommended to install protection devices fuse links or their equivalents int...

Page 7: ...ng in the filling mode with the pressure sensor turn the switch CPG S L CPG Level Sensor to CPG position and turn the switch Drn Fi Drainage Filling to Fi position 3 1 9 By using the handle hs adjust...

Page 8: ...EL liquid level is lower than DR failure of UL LL or DR sensors 1 submersible pump 2 MCK 108 3 dry run sensor electrode 4 electrodes EL emergency level UL upper level LL lower level Com common Figure...

Page 9: ...repeated 3 2 1 4 Operation in the automated drainage mode with the level sensors In the initial state in case the liquid level in the tank is lower than the UL sensor when starting the power supply t...

Page 10: ...s is allowed the LED EL goes out the functional relay deactivates the alarm If the EL sensor is off the LED EL goes out 3 2 3 3 Failures of the pressure level sensors are specified in Table 4 Table 4...

Page 11: ...rer at current rates 5 6 Before sending for repair the product should be packed in the original or other packing excluding mechanical damage Earnest request indicate the reason for return in the notic...