~ 6 ~ 

MCK-108 

    

                                                                                                                                                       

NOVATEK-ELECTRO

 

To  ensure  the  reliability  of  electrical  connections  you  should  use  flexible  (stranded)  wires  with  insulation  for 

voltage  of  not  less  than  450V,  the  ends  of 

which  it  is  necessary  to  be  striped  of  insulation  for  5±0.5  mm  and 

tightened  with  bootlaces.  Recommended  cable  cross  section  for  connection  is  1  mm

2

,

 

not  less

Wires  fastening 

should exclude mechanical damage, twisting and insulation abrasion of wires. 

IT  IS  NOT  ALLOWED  TO  LEAVE  EXPOSED  PORTIONS  OF  WIRE  PROTRUDING  BEYOND  THE 

REMOVABLE TERMINAL BLOCK.  

 

For  reliable  contact  it  is  necessary  to  perform  tightening of  screws of  removable  terminal block with 

the force specified in Table 1.  

When  reducing  the  tightening  torque,  the  junction  point  is  heated,  the  terminal block may  be melted  and wire  can 

burn.  If  you  increase  the  tightening  torque,  it  is  possible  to  have  thread  failure  of  the  terminal  block  screws  or  the 
compression of the connected wire. 

 

To increase the running ability of MCK-108, it is recommended to install protection devices (fuse links 

or their equivalents) into the following circuits (enumerated in the order of necessity, hyphen is followed by 
the recommended protection device rating): 

1) power supply circuits of MCK-108 L, N - 0.5 A; 

 

2)  relay  output  contacts  (protection  device  rating  is  chosen  according  to  the  connected  circuits,  but 

shall not exceed 10 A). 

3.1.3  When  using  the  conduction-measuring  sensor  of  liquid  level  connect  the  device  according  to  power 

according to Figure 2. When using the 

DR

 sensor turn the switch 

Off - DR

 to "

DR

" (Dry Run) position. When using 

the emergency level sensor turn the switch 

Off - EL

 (Off - Emergency Level) to "

EL

" position. 

 

 

 

 
А – controller of MCK-108 
К – contactor starter 
М – electric motor of the pump 
EL 

– emergency level sensor  

 

 
UL 

– upper level sensor  

LL

– lower level sensor  

DR 

– dry run sensor  

Com. 

– common electrode 

– automatic protector 

 

Figure 2

 - Connection Diagram for MCK-108 when working with one pump 

Summary of Contents for MCK-108

Page 1: ...pment and production complies with requirements ISO 9001 2015 Dear customer Company NOVATEK ELECTRO LTD thanks you for purchasing our products You will be able to use properly the product after carefu...

Page 2: ...UT DISCONNECTING THE PRODUCT FROM THE MAINS TO OPEN AND REPAIR THE PRODUCT INDEPENDENTLY TO OPERATE THE PRODUCT WITH MECHANICAL DAMAGES OF THE CASE IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND...

Page 3: ...g the tear and wear the user can set the alternate operation of the pumps To prevent failure of the electric motor while draining the well one may use a dry run sensor conduction measuring dry run sen...

Page 4: ...lling mode it glows red while in the drainage mode it blinks green 13 LED UL Upper Level glows red if the liquid level is higher than the upper level sensor 14 LED EL Emergency Level glows red if the...

Page 5: ...o standard 35 mm DIN rail The device preserves functionality in any position within the space Casing material self extinguishing plastic Table 3 The characteristics of the integrated relays output con...

Page 6: ...ure of the terminal block screws or the compression of the connected wire To increase the running ability of MCK 108 it is recommended to install protection devices fuse links or their equivalents int...

Page 7: ...ng in the filling mode with the pressure sensor turn the switch CPG S L CPG Level Sensor to CPG position and turn the switch Drn Fi Drainage Filling to Fi position 3 1 9 By using the handle hs adjust...

Page 8: ...EL liquid level is lower than DR failure of UL LL or DR sensors 1 submersible pump 2 MCK 108 3 dry run sensor electrode 4 electrodes EL emergency level UL upper level LL lower level Com common Figure...

Page 9: ...repeated 3 2 1 4 Operation in the automated drainage mode with the level sensors In the initial state in case the liquid level in the tank is lower than the UL sensor when starting the power supply t...

Page 10: ...s is allowed the LED EL goes out the functional relay deactivates the alarm If the EL sensor is off the LED EL goes out 3 2 3 3 Failures of the pressure level sensors are specified in Table 4 Table 4...

Page 11: ...rer at current rates 5 6 Before sending for repair the product should be packed in the original or other packing excluding mechanical damage Earnest request indicate the reason for return in the notic...

Reviews: