~ 9 ~ 

NOVATEK-ELECTRO                                                                                                                 MCK-108

 

3.2.1.2 Operation in the automated 

filling mode

 with the pressure sensor 

In the initial state (if the movable contact is located between the 

UL

 and 

LL

 contacts), when starting the power 

supply, the electric motor will not be activated. 

When closing the movable contact with the contact of the 

UL

 upper setting, the automatic deactivation of the 

electric motor takes place. 

When  closing  the  movable  contact  with  the  contact  of  the 

LL

  lower  setting,  the  automatic  activation  of  the 

electric motor takes place and the cycle is repeated. 

 

3.2.1.3 Operation in the automated 

filling mode

 with the level sensors 

In  the  initial  state  (in  case  there  is  no  liquid  in  the  tank),  when  starting  the  power  supply,  the  pump  electric 

motor will be activated automatically. 

When the liquid level reaches the 

UL

 sensor, the automatic deactivation of the electric motor takes place. 

When  the  liquid  level  in  the  tank  is  lower  than  the 

LL

  sensor,  the  automatic  activation  of  the  pump  electric 

motor takes place to feed the liquid into the tank and the cycle is repeated. 

 

3.2.1.4 Operation in the automated 

drainage mode

 with the level sensors 

In  the  initial  state  (in  case  the  liquid  level  in  the  tank  is  lower  than  the 

UL

  sensor),  when  starting  the  power 

supply, the pump electric motor will not be activated. 

When the liquid level reaches the 

UL

 sensor, the automatic activation of the pump electric motor takes place. 

When the liquid level in the tank is lower than the 

LL

 sensor, the automatic deactivation of the pump electric 

motor takes place and the cycle is repeated. 

 

 

 

 

А – MCK-108 controller 
К1,К2 – contactor starter 
М1 – electric motor of the first pump 

М2 – electric motor of the second pump 
S1, S2 

– automatic protectors 

 

 

Figure 7

 

– Connection of two pumps to MCK-108 

 

3.2.2 MCK-108 operation with two pumps 

For operating MCK-108 with two pumps, one must connect the contactor starter of the second pump according to 

Figure 7. 

In the automated operation modes of MCK-108 with two pumps, the operation logic of the device is preserved, but 

the  functional  relay  is  used  to  control  the  electric  motor  of  the  second  pump  and,  subsequently,  does  not  respond  to 
emergency conditions. 

Activation of the electric motors of the pumps (activation of the functional relay and the pump relay) takes place in 

turn after each deactivated of one of them. 

Summary of Contents for MCK-108

Page 1: ...pment and production complies with requirements ISO 9001 2015 Dear customer Company NOVATEK ELECTRO LTD thanks you for purchasing our products You will be able to use properly the product after carefu...

Page 2: ...UT DISCONNECTING THE PRODUCT FROM THE MAINS TO OPEN AND REPAIR THE PRODUCT INDEPENDENTLY TO OPERATE THE PRODUCT WITH MECHANICAL DAMAGES OF THE CASE IT IS NOT ALLOWED WATER PENETRATION ON TERMINALS AND...

Page 3: ...g the tear and wear the user can set the alternate operation of the pumps To prevent failure of the electric motor while draining the well one may use a dry run sensor conduction measuring dry run sen...

Page 4: ...lling mode it glows red while in the drainage mode it blinks green 13 LED UL Upper Level glows red if the liquid level is higher than the upper level sensor 14 LED EL Emergency Level glows red if the...

Page 5: ...o standard 35 mm DIN rail The device preserves functionality in any position within the space Casing material self extinguishing plastic Table 3 The characteristics of the integrated relays output con...

Page 6: ...ure of the terminal block screws or the compression of the connected wire To increase the running ability of MCK 108 it is recommended to install protection devices fuse links or their equivalents int...

Page 7: ...ng in the filling mode with the pressure sensor turn the switch CPG S L CPG Level Sensor to CPG position and turn the switch Drn Fi Drainage Filling to Fi position 3 1 9 By using the handle hs adjust...

Page 8: ...EL liquid level is lower than DR failure of UL LL or DR sensors 1 submersible pump 2 MCK 108 3 dry run sensor electrode 4 electrodes EL emergency level UL upper level LL lower level Com common Figure...

Page 9: ...repeated 3 2 1 4 Operation in the automated drainage mode with the level sensors In the initial state in case the liquid level in the tank is lower than the UL sensor when starting the power supply t...

Page 10: ...s is allowed the LED EL goes out the functional relay deactivates the alarm If the EL sensor is off the LED EL goes out 3 2 3 3 Failures of the pressure level sensors are specified in Table 4 Table 4...

Page 11: ...rer at current rates 5 6 Before sending for repair the product should be packed in the original or other packing excluding mechanical damage Earnest request indicate the reason for return in the notic...

Reviews: