Section 3: Operation of the Control Panel
3.1 Overview
This section contains instructions for operating the control panel. Listed below are the topics
detailed in this section:
This manual also contains information on operating the control panel in the appendixes, listed as
follows:
•
Appendix A, “Special Zone Operation”, on page 49
•
Appendix B, “Intelligent Detector Functions”, on page 58
•
Appendix C, “Remote Terminal Access”, on page 60
•
Appendix D, “Point and System Troubles Lists”, on page 68
3.2 Normal Mode of Operation
The system operates in Normal mode when no alarms or troubles exist. In Normal mode, the
control panel displays a System Normal message as follows
Figure 3.1 Sample System Normal Message
Section
Refer to Page
3.2, "Normal Mode of Operation"
3.3, "Fire Alarm Mode of Operation"
3.4, "System Trouble Mode of Operation"
3.5, "Security Alarm Mode of Operation"
3.6, "Active Supervisory Signal Mode of Operation"
3.7, "Pre-Alarm Warning Mode of Operation"
3.8, "Disabled Points Mode of Operation"
3.9, "Non-Alarm Mode of Operation"
3.10, "CO Alarm Mode of Operation"
3.11, "Active Trouble Monitor Mode of Operation"
3.11, "Active Trouble Monitor Mode of Operation"
3.12, "Output Circuit Trouble Mode of Operation"
3.13, "Operation of Special System Timers"
3.14, "Waterflow Circuit Operation"
3.15, "Style 6 and Style 7 Operation"
!
WARNING:
When used for CO
2
releasing applications, observe proper precautions as stated in NFPA 12. Do not
enter the protected space unless physical lockout and other safety procedures are fully completed.
Do not use software disable functions in the panel as lockout.
S Y S T E M N O R M A L 0 1 : 5 6 P 0 4 1 5 0 8 S a t