NFS2-640/E Operations Manual —
P/N 52743:F1 06/16/2011
63
Using the CRT-2 for Read Status
Remote Terminal Access
From the Read Status menu, you can select options 1-7.
C.3.3 Read Point
From the Read Status menu, select option
1
- Read Point. The CRT-2 displays the following:
Enter the following:
1.
Enter the SLC number “1” or “2”.
2.
Enter the first letter of the device, using upper case letters.
• Detector = “D”
• Module = “M”
• Zone = “Z”
• Special Function = “F”
• Releasing Zone = “R”
• E Zone = “E”
• L Zone = “L”
• System Parameter = “S”
3.
Enter the address or number of the device.
4.
Press “
ENTER
”.
Example
Read points for detectors 1D001 and 1D002 on SLC 1:
C.3.4 Display Devices in Alarm or Trouble
From the “Read Status” menu, select option
2
- Read Alarms/Troubles. The CRT-2 will display the
alarm and trouble history.
Press <
1
> <
ENTER
>
Type (n)D(nnn), (n)M(nnn), Z(nn), F(n),, R(n), Ex, Lx or S(n) then hit Enter
SLC number
Address )01-159)
Number
NOTE:
Press
F5
to scroll forward through a list of devices. Press
F6
to scroll back through a list
of devices.
NORMAL SMOKE(PHOTO) INTENSIVE CARE UNIT NURSE LOUNGE Z050 020%A6 6 CV30 1D001
Press <
1
> <
D
> <
0
> <
0
> <
1
> <
ENTER
>
NORMAL SMOKE (ION) DETECTOR ADDR 1D002 Z002 000%A6 6 ** 1D002
Press <
NEXT
>