10
NFS2-640/E Operations Manual —
P/N 52743:F1 06/16/2011
General Information
Introduction to the Control Panel
1.2.4 Shortcuts to Operating Functions
To the left of each program function, you’ll find a keypad shortcut, which contains a
series of keypad entries required to access the program function. All shortcuts start
with the control panel in normal operation.
For example, the keypad shortcut to the left, shows how to enter the Read Status
function with the control panel in normal operation, as well as how to exit the
function.
1.3 Introduction to the Control Panel
The NFS2-640 is a modular, intelligent Fire Alarm Control Panel (FACP) with features suitable for
most applications. Following is a list of operating features available.
•
Alarm Verification selection, to reduce unwanted alarms, for intelligent detector points
•
Positive Alarm Sequence (PAS) and Presignal per NFPA 72
•
Silence Inhibit timer and Auto Silence timer for Notification Appliance Circuits (NACs)
•
March time/temporal code for Notification Appliance Circuits (NACs)
•
Programmable Signal Silence, System Reset, and Alarm Activate functions through monitor
modules
•
Automatic time-of-day and day-of-week control functions, with holiday option
•
Intelligent Sensing with nine field-adjustable Pre-Alarm levels with programmable
Control-By-Event (CBE)
•
Operate automatic smoke or heat detector sounder base on action Pre-Alarm level, with
general evacuation on alarm level
•
Security alarm point option with separate audible signal code
•
Centralized voice paging and audible alarm signaling options
•
Programmable Control-By-Event control of outputs from individual alarm or supervisory
addressable devices
•
Networks with other FACPs and equipment for large applications.
TM-4 Installation Document (Reverse Polarity Transmitter)
51490
UDACT Manual (Universal Digital Alarm Communicator/Transmitter)
50050
ACT-2 Installation Document
51118
FireVoice 25/50 & FireVoice 25/50ZS Manual
52290
RM-1 Series Remote Microphone Installation Document
51138
RA400Z Remote LED Annunciator Installation Document
I56-508
XP10-M Installation Document
I56-1803
XP6-C Installation Document
I56-1805
XP6-MA Installation Document
I56-1806
XP6-R Installation Document
I56-1804
LCD-80 Liquid Crystal Display Remote Annunciator
15037
LCD2-80 Liquid Crystal Display Remote Annunciator
53242
Table 1.2 Supplemental Documentation (2 of 2)