Chapter 9 — NTMW05 Digital Line Card
Page 95 of 136
Meridian 1 Option 11C Compact
Technical Reference Guide
Technical summary
Table 32 provides a technical summary of the digital line card.
Table 32
NTMW05 Digital Line Card technical summary
Power requirements
The digital line card needs +15V DC over each loop at a maximum current of
80 mA. It re15V, - 15V, and +5V from the backplane. The line feed
interface can supply power to one loop of varying length up to 3500 ft
(1070 m) using 24 AWG wire with a maximum allowable AC signal loss of
15.5 dB at 256 kHz, and a maximum DC loop resistance of 210 ohms;
26 AWG wire is limited to 2450 ft (745 m).
Foreign and surge voltage protections
In-circuit protection against power line crosses or lightning is not provided on
the Digital line card.
Characteristics
Description
Units per card
24 voice, 8 data
Impedance
100 ohms
Loop limits
0 to 3500 ft (1070 m) with 24 AWG cable
(+15 V DC at 80 mA)
0 to 2450 ft (745 m) with 26 AWG cable
Line rate
512 kbps + 100 ppm
Power supply
+ 5 V DC
+15 V DC
+10 V DC
Transmitter output voltage:
—successive “1” bits
+1.5 + 0.15 V and -1.5 + 0.15 V
—”0” bits
0 + 50 mV
Summary of Contents for Meridian 1 Option 11C Compact
Page 3: ...553 3121 100 Standard 2 0 September 1998 ...
Page 11: ...viii About this guide 553 3121 100 Standard 2 0 September 1998 ...
Page 21: ...Page 10 of 136 Chapter 1 Provisioning 553 3121 100 Standard 2 0 September 1998 ...
Page 41: ...Page 30 of 136 Chapter 2 Transmission parameters 553 3121 100 Standard 2 0 September 1998 ...
Page 63: ...Page 52 of 136 Chapter 6 SDI ports 553 3121 100 Standard 2 0 September 1998 ...
Page 103: ...Page 92 of 136 Chapter 8 M2250 Attendant Console 553 3121 100 Standard 2 0 September 1998 ...
Page 107: ...Page 96 of 136 Chapter 9 NTMW05 Digital Line Card 553 3121 100 Standard 2 0 September 1998 ...