2. Installation.
I
t is strongly advised that the installer reads Section 1 of
this manual prior to starting any installation work. It is a
requirement that only qualifi ed and competent personnel
undertake installation, commissioning, and servicing.
Warning
Always ensure that the appropriate personal protective
equipment is used.
2.1 Packaging/siting
The heater will usually be supplied wrapped in heavy gauge
polythene, non assembled parts will be supplied separately.
Prior to installation, the assembly of the heater should be
completed, it is advisable that this is undertaken in the area
where the heater is scheduled to be sited.
Caution
It is strongly advised that when positioning the heater the
lifting eyes are used, thereby reducing the risk of inadvertent
damage being occasioned to the heater.
2.2
Flooring
The heater must be installed on a level non-combustible
surface capable of supporting the weight of the heater and
any ancillary equipment.
2.3
Minimum clearances
The following minimum clearances (in millimeters) are
recommended when installing the heater.
Model
Front
Rear
LHS
RHS
30 - 40
500
700
150
150
60 - 85
500
1000
150
150
120 - 135
600
1200
150
150
180
600
1500
150
150
205
900
1500
150
150
235 - 300
900
2000
400
400
375
900
2000
500
500
2.4
Assembly
The following sub-assembly parts should be assembled to
allow installation to continue.
(a) Vertical Nozzled Models
For free blowing applications it will be necessary to complete
the fi nal assembly before continuing with the installation. The
bonnet top with nozzle spigots should be attached to the
heater and secured. The nozzles should then be pushed home
on the spigots and positioned to provide the desired airfl ow.
Ensure louvres are adjusted outwards and ensure blades are
not resonating.
The nozzles should be securely fi xed in their desired position
on completion of commissioning.
(b) Horizontal Nozzled Models
Remove packaging and secure the 90° Duct Outlet to the
outlet on the heater using the bolts supplied.
Secure the nozzle spigot plate to the duct outlet using the
bolts and prevailing torque nuts provided. Fit the securing
brackets to each of the outlet nozzles, and lift the complete
heater assembly and position on the pre-sited purpose built
supports. Finish off the assembly by fi tting and securing the
outlet nozzles to the spigots by way of previously fi tted
brackets.
2.5
Flue Installation
An integral fl ue spigot is fi tted to all Cabinet Heaters thereby
allowing the fl ue to connect directly to the heater.
The design of the fl ue must ensure that it can be disconnected
to allow for cleaning and servicing, furthermore, all of the fl ue
section joint sockets must face upwards, and the seal between
the sections achieved through mechanical joints or through
the use of approved caulking string and grout.
Caution
It is strongly advised that BS 5854 and BS 5440 parts 1 and 2
are referred to. See also terminal details on page 15 & 16
Where condensation is likely to be a problem provision should
be made preferably at the design stage (see section 1.13)
Summary of Contents for Reznor 120
Page 28: ...Wiring Diagram 20 45 600 30 40 ON OFF Riello Burner Integral SC SZ 230 50 1ph...
Page 29: ...Wiring Diagram 20 45 601 60 85 ON OFF Riello Burner Integral SC SZ 230 50 1ph...
Page 30: ...Wiring Diagram 20 45 602 120 135 ON OFF Riello Burner Integral SC SZ 230 50 1ph...
Page 31: ...Wiring Diagram 20 45 603 60 300 ON OFF Riello Burner Integral SC SZ 415 50 3ph...
Page 32: ...Wiring Diagram 20 45 616 30 40 ON OFF Riello Burner Remote SC SZ 230 50 1ph...
Page 33: ...Wiring Diagram 20 45 617 60 85 ON OFF Riello Burner Remote SC SZ 230 50 1ph...
Page 34: ...Wiring Diagram 20 45 618 120 135 ON OFF Riello Burner Remote SC SZ 230 50 1ph...
Page 35: ...Wiring Diagram 20 45 619 60 300 ON OFF Riello Burner Remote SC SZ 415 50 3ph...
Page 36: ...Wiring Diagram 20 45 604 30 40 ON OFF Riello Burner Integral CP4 230 50 1ph...
Page 37: ...Wiring Diagram 20 45 605 60 85 ON OFF Riello Burner Integral CP4 230 50 1ph...
Page 38: ...Wiring Diagram 20 45 606 120 135 ON OFF Riello Burner Integral CP4 230 50 1ph...
Page 39: ...Wiring Diagram 20 45 607 60 300 ON OFF Riello Burner Integral CP4 415 50 3ph...
Page 40: ...Wiring Diagram 20 45 620 30 40 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 41: ...Wiring Diagram 20 45 621 60 85 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 42: ...Wiring Diagram 20 45 622 120 135 ON OFF Riello Burner Remote CP4 230 50 1ph...
Page 43: ...Wiring Diagram 20 45 623 60 300 ON OFF Riello Burner Remote CP4 415 50 3ph...
Page 44: ...Wiring Diagram 20 45 612 30 40 ON OFF Riello Burner No Controls 230 50 1ph...
Page 45: ...Wiring Diagram 20 45 613 60 85 ON OFF Riello Burner No Controls 230 50 1ph...
Page 46: ...Wiring Diagram 20 45 614 120 135 ON OFF Riello Burner No Controls 230 50 1ph...
Page 47: ...Wiring Diagram 20 45 615 60 300 ON OFF Riello Burner No Controls 415 50 3ph...
Page 55: ...5 Parts Lists...
Page 66: ...Notes...
Page 67: ...Notes...