Nortek R8GE Series Installation Instructions Manual Download Page 19

19

1. Shut off the gas supply to the unit at the meter or at the 

manual valve in the gas supply piping.

2. Turn off all power to the unit and set the thermostat to the 

lowest temperature setting.

3. Remove the louvered access panel from the unit.

4. Turn the gas control knob (gas valve) to the OFF position. 

See 

Figure 10 (page 24)

 for gas valve shut off instructions.

5. Disconnect the wires from the gas valve, ignitor, flame 

sensor, combustion air motor, flame roll-out control, over-

temperature limit switch, and pressure switch.

6. Remove the silicone rubber tube from the collector pan to 

the pressure switch.

7. Remove 4 nuts securing the combustion blower to the 

collector pan. Remove the combustion blower.

8. Remove all screws securing the collector pan to the unit. 

Remove the collector pan from the unit.

 CAUTION:

To prevent damage to the unit or internal components, 

it is recommended that two wrenches be used when 

loosening or tightening nuts. Do not over tighten!

9. Using 2 wrenches, separate the ground-joint union in the 

gas supply piping at the unit.

10. Remove the piping between the gas valve and the ground-

joint union, if necessary.

11. Remove the screws that secure the burner assembly in place 

and the burner assembly.

 BE EXTREMELY CAREFUL 

NOT TO DAMAGE THE IGNITOR WHILE REMOVING 

THE BURNER ASSEMBLY.

12. Attach a round wire brush to a length of high grade stainless 

steel cable, such as drain clean-out cable. Attach the other 

end of the spring cable to a variable speed reversible drill. 

Slowly insert and rotate the cable into the top portion of 

the heat exchanger. Operate the drill alternating between 

forward and reverse, working the cable in and out several 

times to obtain sufficient cleaning. Repeat this process at 

each exchanger tube.

13. Remove all loosened debris from the heat exchanger tubes 

using high pressure air and vacuum cleaner.

14. Using a light, check the condition of the upper and lower 

sections of the heat exchanger tube.

15. Inspect the burners and if necessary, clean them carefully 

with a soft wire brush and/or the nozzle of a vacuum cleaner. 

DO NOT DAMAGE THE IGNITOR OR FLAME SENSOR 

WHILE CLEANING THE BURNER.

16. Replace all the parts in reverse order from which they were 

removed.

17. Follow the operating instructions found on the right side 

door and the User’s Information Manual to return the unit 

to operation.

Cleaning of Burners

If the burners must be cleaned, follow the steps below.

1. Shut off the gas supply to the unit either at the meter or at 

a manual valve in the supply piping.

2. Turn off all power to the unit and set the thermostat to the 

lowest temperature setting.

3. Remove the louvered control access panel from the unit.

4. Turn the gas control knob to the OFF position. See 

Figure 

10 (page 24)

 for gas valve shut off instructions.

5. Disconnect the wires from the gas valve, ignitor, and flame 

sensor.

 CAUTION:

Use care when removing parts from this unit. 

Personal injury can result from sharp metal edges 

present in all equipment of sheet metal construction.

Proper maintenance is important to achieve optimum 

performance from the system. The ability to properly perform 

maintenance on this equipment requires certain mechanical 

skills and tools. If you do not possess these skills, contact your 

dealer for maintenance. Consult your local dealer about the 

availability of maintenance contracts. Routine maintenance 

should include the following:

 CAUTION:

The unit should never be operated without a filter 

in the return air system. Replace disposable filters 

with the same type and size.

•  Inspect, clean or replace air filters at the beginning of each 

heating and cooling season, or more frequently if required.

• Inspect the condensate drain and outdoor coil at the 

beginning of each cooling season. Remove any debris. 

Clean the outdoor coil and louvers as necessary using a 

mild detergent and water. Rinse thoroughly with water.

• Inspect the electrical connections for tightness at the 

beginning of each heating and cooling season.

•  The blower compartment should be cleaned monthly during 

the heating and cooling seasons to remove any dirt and lint 

that may have accumulated in the compartment or on the 

blower and motor. Buildup of dirt and lint on the blower and 

motor can create excessive loads on the motor resulting in 

higher than normal operating temperatures and possible 

shortened service life.

• Maintain heat exchanger and burners. The unit should 

operate for many years without excessive scale buildup in 

the heat exchanger, however, the heat exchanger, the vent 

system, and the burners should be inspected and cleaned 

(if required) by a qualified serviceman annually to ensure 

continued safe operation. Particular attention must be given 

to identify deterioration from corrosion or other sources.

•  The motors for the circulating air blower, outdoor fan, and 

combustion blower are pre-lubricated at the factory. No 

further oiling is required for the life of this product.

•  Inspect and clean the screen of the vent cover assembly 

at the beginning of each heating and cooling season.

Cleaning of Heat Exchanger

 WARNING:

Holes in the heat exchanger can cause products 

of combustion to enter the home. Replace the heat 

exchanger if leaks are found. Failure to prevent 

products of combustion from being circulated into 

the living space can create potentially hazardous 

conditions including carbon monoxide poisoning 

that could result in personal injury or death.

If the heat exchanger must be cleaned due to soot or scale 

build up, follow the steps below.

Summary of Contents for R8GE Series

Page 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflamma...

Page 2: ...P Propane Gas Conversion 15 START UP ADJUSTMENTS 16 Pre Start Check List 16 Start Up Procedure 16 Air Circulation 16 System Cooling 16 System Heating 16 Verifying Adjusting Temperature Rise 16 Verifyi...

Page 3: ...brancher S assurer de les raccorder correctement S assurer que l appareil fonctionne ad quatement apr s l entretien WARNING TheseunitsarefullychargedwithR 410Arefrigerant andreadyforinstallation When...

Page 4: ...d the air vent intake terminal See page 8 Combustionproductsmustbedischargedoutdoors Connect this unit to an approved vent system only as specified on page 8 Never test for gas leaks with an open flam...

Page 5: ...nt Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructions D gaugement conforme aux codes d installation locaux aux...

Page 6: ...s suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapessuivantesdoivent tresuivi...

Page 7: ...als Carbon tetrachloride Halogen type refrigerants Cleaning solvents Cements glues paint removers varnishes etc Hydrochloric acid Masonry acid washing materials Plumbing Stack Venting Requirements Thi...

Page 8: ...ing operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under norma...

Page 9: ...tbelocatedaccordingtolocalbuilding codes or ordinances and these requirements The roof must be capable of handling the weight of the unit For unit weights see Table 9 page 21 Reinforce the roof if nec...

Page 10: ...ove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Remo...

Page 11: ...iring methods must be acceptable to authority having jurisdiction Useonlycopperwireforthelinevoltagepowersupplytothis unit See Table 4 page 12 Use proper code agency listed conduit and a conduit conne...

Page 12: ...225 110 Table 5 Thermostat Wire Gauge Table 3 Electrical Data MODEL NUMBER HEATING INPUT BTUH NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAX...

Page 13: ...lating blower motor has started Set the heat anticipator according to the thermostat manufacturer s instructions for heat anticipator settings Blower Speed The blower speed is preset at the factory fo...

Page 14: ...tbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases GAS SUPPLY PIPING WARNING FIRE OR...

Page 15: ...e carbon monoxide poisoning personal injury or death Conversion of this equipment to LP Propane gas must be made by qualified service personnel using approved factory parts Conversion to LP can be acc...

Page 16: ...andverifythecompressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for any unusual noises If unusua...

Page 17: ...operates for more thanfourminuteswithnoreturnair setthethermostatbelow room temperature shut off power to the unit and replace the over temperature limit control Verifying Burner Operation WARNING Un...

Page 18: ...ignition the furnace control is locked and the red LED will blink 4 times repetitively The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out Otherwise t...

Page 19: ...e unit 4 Turn the gas control knob to the OFF position See Figure 10 page 24 for gas valve shut off instructions 5 Disconnect the wires from the gas valve ignitor and flame sensor CAUTION Use care whe...

Page 20: ...ustion blower will continue to operate if the flame roll out control opens Flame Sensor Proves that flame has carried over from the ignitor to the right most burner If no flame is sensed the unit will...

Page 21: ...al Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 R8GE Dimensions Table 9 Center of Gravity Unit Shipping Weights Model Numb...

Page 22: ...62 1113 66 T3 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T4 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T5 2015 37 1970 37 1915 39 1870 39 1805 41 1740 42 168...

Page 23: ...E REVOLUTION SECONDS CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 1...

Page 24: ...utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Nejamaisutiliserd outils S iln estpaspo...

Page 25: ...SE FLAME OR GAS RELAY SHORTED PRESURE SWITCH STUCK OPEN WITH INDUCER ON PRESURE SWITCH STUCK CLOSED WITH INDUCER OFF WIRING DIAGRAM FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 10076210 05 15 FLAME ST...

Page 26: ...NGE BLUE RED GREEN YELLOW RED RED ORANGE WHITE WHITE BLUE YELLOW BLACK GREY GREEN BLACK BLACK GREEN WHITE YELLOW RED WHITE BLACK YELLOW 460 Volt Three Phase 60Hz 3 If any of the original wire as suppl...

Page 27: ...EFRIGERANT WHEN BELOW CURVE R8GE X36C X48C X60C Charging Chart Cooling Figure 13 Charging Chart for 3 Ton Units 3 5 TON MODELS 4 TON MODEL 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 5...

Page 28: ...Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity...

Reviews: