A. This appliance does not have a pilot. It is equipped with 

an ignition device which automatically lights the burner. 

Do not try to light the burner by hand.

B. BEFORE OPERATING smell all around the appliance 

area for gas. Be sure to smell next to the floor because 

some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

•  Do not try to light any appliance.

•  Do not touch any electrical switch; do not use any phone 

in your building.

•  Immediately call your gas supplier from a neighbor’s 

phone. Follow the gas supplier’s instructions.

•  If you cannot reach your gas supplier, call the fire 

department.

C. Use only your hand to push in or turn the gas control 

knob. Never use tools. If the knob will not push in or move 

by hand, do not try to repair it, call a qualified service 

technician. Force or attempted repair may result in a fire 

or explosion.

D. Do not use this appliance if any part has been under water. 

Immediately call a qualified service technician to inspect 

the appliance and to replace any part of the control system 

and any gas control which has been under water.

 1. 

ATTENTION!

 Lire d’abord la liste des mesures de sécurité 

ci-dessus.

  2. Mettre le thermostat à la position minimale.

  3. Couper le courant électrique qui mène à l’appareil.

  4.  Cet appareil ménager étant doté d’un système d’allumage 

automatique, ne pas essayer d’allumer le brûleur 

manuellement.

  5. Retirer le panneau/volet d’accès de commande (panneau 

supérieur s’il s’agit d’un modèle à deux panneaux).

  6. Règlez I’nterrupteur de commande du gaz à la position 

“OFF” (Arrêt) (Voir Figure).

  7.  Attendre cinq (5) minutes pour s’assurer de la dissipation 

du gaz.

 

En cas d’odeur, ARRÊTER LE PROCÉDÉ. Suivre les 

instructions ci-dessus (Section B). En l’absence de toute 

odeur de gaz, avancer à l’étape suivante.

  8. Règlez I’nterrupteur de commande du gaz à la position 

“OFF” (Arrêt) (Voir Figure).

 9. Remettre le panneau/volet d’accès de commande en 

place (panneau supérieur s’il s’agit d’un modèle à deux 

panneaux).

10. Rebrancher l’appareil sur le réseau électrique.

11. Ajuster le thermostat à la position désirée.

12. Si l’appareil ne fonctionne pas, suivre les “Directives 

d’arrêt” cidessous et appeler le technicien de service.

A. Cet appareil ménager n’a pas de veilleuse. II est doté 

d’un système d’allumage automatique. Ne pas essayer 

d’allumer le brûleur manuellement.

B. AVANT L’USAGE. Attention à une possible odeur de gaz 

surtout au niveau du plancher où les gaz les plus lourds 

ont la tendance de se concentrer.

EN CAS D’ODEUR DE GAZ.

•  Ne mettre en marche aucun appareil électrique.

•  Ne toucher à aucun commutateur électrique, ne pas 

employer le téléphone.

•  Quitter le bâtiment immédiatement et avertir la compagnie 

du gaz en utili sant le téléphone d’un voisin.

•  A défaut de la compagnie du gaz, avertir le service des 

pompiers.

C. Enfoncer ou faire tourner le robinet à gaz à la main 

seulement. Ne jamais utiliser d’outils. S’il n’est pas possible 

de faire tourner ou d’enfoncer le robinet à la main, ne pas 

essayer de le réparer. Faire appel à un spécialiste. Forcer 

ou tenter de réparer le robinet pourrait être à l’origine d’une 

explosion ou d’un incendie.

D.  II est déconseillé d’utiliser cet appareil en contact prolongé 

avec l’eau. Faire inspecter ou remplacer toute commande 

par un technicien qualifié si un des systèmes de contrôle 

du gaz s’est trouvé sous l’eau.

 1. 

STOP!

 Read the safety information above on this label.

  2. Set the thermostat to the lowest setting.

  3. Turn off all electrical power to the appliance.

  4. The appliance’s ignition device automatically lights the 

burner. Do not try to light burner by hand.

  5. Remove the control access door/panel (upper door if 

two-door model).

  6. Move the gas control switch to the “OFF” position. (See 

Figure 1)

  7. Wait five (5) minutes to clear out any gas. Then smell 

for gas, including near 

the floor. If you smell 

gas, STOP! Follow “B” 

in above information. If 

you don’t smell gas, go 

to the next step.

  8. Move the gas control 

switch to the “ON” 

position. (See Figure)

  9. Replace the control 

access door/panel 

(upper door if two-door model).

10. Turn on all electrical power to the appliance.

11. Turn the thermostat to a desired setting.

12. If the appliance will not operate, follow the instructions 

“To Turn Off Gas To Appliance” and call your service 

technician or gas supplier.

  1. Mettre le thermostat à la position minimale.

  2. Débrancher l’appareil en prévision de la réparation.

  3. Retirer le panneau/volet d’accès de commande (panneau 

supérieur s’il s’agit d’un modèle à deux panneaux).

  4. Règlez I’nterrupteur de commande du gaz à la position 

“OFF”. Ne forcez pas. (Voir Figure).

 5. Remettre le panneau/volet d’accès de commande en 

place (panneau supérieur s’il s’agit d’un modèle à deux 

panneaux).

POUR VOTRE SÉCURITÉ. À LIRE AVANT L’EMPLOI

FOR YOUR SAFETY READ BEFORE OPERATING

  1. Set the thermostat to the lowest setting.

  2. Turn off all electrical power to the appliance if service is 

to be performed.

 3. Remove the control access door/panel (upper door if 

two-door model).

  4. Move the gas control knob switch to the “OFF” position. 

Do not use force. (See Figure)

 5. Replace the control access door/panel (upper door if 

two-door model).

ATTENTION!

 L’inobservation de ces instructions peut 

entraîner un incendie ou une explosion pouvant causer 

des dam mages à votre propriété à votre personne, ou 

la mort.

WARNING:

 If you do not follow these instructions 

exactly, a fire or explosion may result causing property 
damage, personal injury, or loss of life.

TURNING GAS OFF TO THE APPLIANCE

DIRECTIVES D’ARRÊT

Figure

SWITCH

(INTERRUPTEUR)

OPERATING INSTRUCTIONS

MODE D’EMPLOI

Figure 10. R8GE Gas Valve Label

Summary of Contents for R8GE Series

Page 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflamma...

Page 2: ...P Propane Gas Conversion 15 START UP ADJUSTMENTS 16 Pre Start Check List 16 Start Up Procedure 16 Air Circulation 16 System Cooling 16 System Heating 16 Verifying Adjusting Temperature Rise 16 Verifyi...

Page 3: ...brancher S assurer de les raccorder correctement S assurer que l appareil fonctionne ad quatement apr s l entretien WARNING TheseunitsarefullychargedwithR 410Arefrigerant andreadyforinstallation When...

Page 4: ...d the air vent intake terminal See page 8 Combustionproductsmustbedischargedoutdoors Connect this unit to an approved vent system only as specified on page 8 Never test for gas leaks with an open flam...

Page 5: ...nt Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructions D gaugement conforme aux codes d installation locaux aux...

Page 6: ...s suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapessuivantesdoivent tresuivi...

Page 7: ...als Carbon tetrachloride Halogen type refrigerants Cleaning solvents Cements glues paint removers varnishes etc Hydrochloric acid Masonry acid washing materials Plumbing Stack Venting Requirements Thi...

Page 8: ...ing operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under norma...

Page 9: ...tbelocatedaccordingtolocalbuilding codes or ordinances and these requirements The roof must be capable of handling the weight of the unit For unit weights see Table 9 page 21 Reinforce the roof if nec...

Page 10: ...ove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Remo...

Page 11: ...iring methods must be acceptable to authority having jurisdiction Useonlycopperwireforthelinevoltagepowersupplytothis unit See Table 4 page 12 Use proper code agency listed conduit and a conduit conne...

Page 12: ...225 110 Table 5 Thermostat Wire Gauge Table 3 Electrical Data MODEL NUMBER HEATING INPUT BTUH NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAX...

Page 13: ...lating blower motor has started Set the heat anticipator according to the thermostat manufacturer s instructions for heat anticipator settings Blower Speed The blower speed is preset at the factory fo...

Page 14: ...tbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases GAS SUPPLY PIPING WARNING FIRE OR...

Page 15: ...e carbon monoxide poisoning personal injury or death Conversion of this equipment to LP Propane gas must be made by qualified service personnel using approved factory parts Conversion to LP can be acc...

Page 16: ...andverifythecompressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for any unusual noises If unusua...

Page 17: ...operates for more thanfourminuteswithnoreturnair setthethermostatbelow room temperature shut off power to the unit and replace the over temperature limit control Verifying Burner Operation WARNING Un...

Page 18: ...ignition the furnace control is locked and the red LED will blink 4 times repetitively The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out Otherwise t...

Page 19: ...e unit 4 Turn the gas control knob to the OFF position See Figure 10 page 24 for gas valve shut off instructions 5 Disconnect the wires from the gas valve ignitor and flame sensor CAUTION Use care whe...

Page 20: ...ustion blower will continue to operate if the flame roll out control opens Flame Sensor Proves that flame has carried over from the ignitor to the right most burner If no flame is sensed the unit will...

Page 21: ...al Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 R8GE Dimensions Table 9 Center of Gravity Unit Shipping Weights Model Numb...

Page 22: ...62 1113 66 T3 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T4 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T5 2015 37 1970 37 1915 39 1870 39 1805 41 1740 42 168...

Page 23: ...E REVOLUTION SECONDS CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 1...

Page 24: ...utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Nejamaisutiliserd outils S iln estpaspo...

Page 25: ...SE FLAME OR GAS RELAY SHORTED PRESURE SWITCH STUCK OPEN WITH INDUCER ON PRESURE SWITCH STUCK CLOSED WITH INDUCER OFF WIRING DIAGRAM FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 10076210 05 15 FLAME ST...

Page 26: ...NGE BLUE RED GREEN YELLOW RED RED ORANGE WHITE WHITE BLUE YELLOW BLACK GREY GREEN BLACK BLACK GREEN WHITE YELLOW RED WHITE BLACK YELLOW 460 Volt Three Phase 60Hz 3 If any of the original wire as suppl...

Page 27: ...EFRIGERANT WHEN BELOW CURVE R8GE X36C X48C X60C Charging Chart Cooling Figure 13 Charging Chart for 3 Ton Units 3 5 TON MODELS 4 TON MODEL 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 5...

Page 28: ...Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity...

Reviews: