Nortek R8GE Series Installation Instructions Manual Download Page 9

9

UNIT INSTALLATION

Packaging Removal

Remove the shipping carton and User’s Manual from the 

equipment. Take care not to damage the tubing connections 
when removing the carton. For rooftop installations, remove 
and discard the two supports attached beneath the unit.

Rigging & Hoisting

 WARNING:

To avoid the risk of property damage, personal injury, 

or death, it is the rigger’s responsibility to ensure 

that whatever means are used to hoist the unit are 

safe and adequate:

• The lifting equipment must be adequate for the 

load. Refer to 

Table 9 (page 21)

 for unit weights.

•  The unit must be lifted from the holes in the base 

rails using cables or chains.

•  Spreader bars are required to protect the unit and 

ensure even loading.

•  Keep the unit in an upright position at all times. The 

rigging must be located outside the units center 

of gravity. Refer to 

Figure 9 (page 21)

 for locating 

the center of gravity.

•  All panels must be securely in place during rigging 

and hoisting.

Clearances to Combustible Materials

R8GE units are certified as combination heating and cooling 

equipment for outdoor rooftop or ground level installations. 

Units may be installed on combustible flooring or Class A, 

B, or C roofing material when used with bottom supply and 

return air ducts as long as the following requirements are met:

•  If using horizontal supply and return air ducts, the horizontal 

roof curb kit and return air kit must be installed prior to unit 

installation. Horizontal roof curb is required.

•  If using bottom discharge with return air ducts a roof curb 

must be installed prior to unit installation. See Rigging and 

Hoisting section for setting of the unit.

•  Sufficient clearance for unobstructed airflow through the 

outdoor coil must also be maintained in order to achieve 

rated performance. See 

page  5

 for information about 

locating the equipment.

Ground Level

Ground level installations must be located according to local 

building codes or ordinances and these requirements:

•  Clearances must be in accordance with those shown in 

Figure 3 (page 10)

.

•  A suitable mounting pad (

Figure 3

) must be provided and 

be separate from the building foundation. The pad must 

be level to ensure proper condensate disposal and strong 

enough to support the unit’s weight. The slab height must 

be a minimum of 2” (5cm) above grade and with adequate 

drainage.

• Units require horizontal roof curb and return air kit for 

horizontal installations.

•  Ductwork should be attached directly to flanges on panels 

supplied in horizontal duct conversion kits.

Rooftop

Rooftop installations must be located according to local building 

codes or ordinances and these requirements:

•  The roof must be capable of handling the weight of the unit. 

For unit weights, see 

Table 9 (page 21)

. Reinforce the 

roof if necessary.

•  The appropriate accessory roof curb must be installed prior 

to unit installation. The roof curb must be square and level 

to ensure proper condensate drainage. See 

Figure 4 (page 

10)

Please follow all instructions provided with the 

kit.

• Secure roof curb or frame to roof using acceptable 

mechanical methods per local codes. 

NOTE:

 Make sure the 

two supports beneath the unit have been removed.

Condensate Drain

Condensate is removed from the unit through the 3/4” female 

pipe fitting located on the front side of the unit. See 

Figure 5 

(page 10)

. Install a 2 inch condensate trap in the drain line of 

the same size and prime with water. When connecting rigid drain 

line, hold the female fitting with a wrench to prevent twisting. 

Do not over tighten!

 Refer to local codes and restrictions 

for proper condensate disposal requirements.

Horizontal to Downflow Conversion

The unit is shipped ready for horizontal duct connections. 

If down flow ducts are required, the unit must be converted 

following the steps below for both the supply and return ducts.

1. Remove the horizontal duct cap.

2. Locate the duct cap inside the duct openings and remove 

the screw holding it in place.

3. Lift the cap out of the unit. (

Hint: 

The cap can be pushed 

up from the bottom by reaching through the fork slot).

4. Cover the horizontal duct opening with the horizontal duct 

cap. The insulation will be on the indoor side.

5. Fasten the cover with screws to seal.

Removal of Internal Filter Rack

(3 Phase Only)

1. Remove the return air panel from the unit.

2. Remove the height adjustment screw from the inside of the 

rack.

3. Remove (1) screw securing the assembly to the coil located 

on the left leg of the rack. 

NOTE:

 The assembly can now 

be easily collapsed and removed from the unit. See 

Figure 

6 (page 10)

 for filter rack securing screw locations.

Installing Filters in the Filter Rack (3 Phase Only)

1. Remove access panel screws from return air panel. 

(

HINT

: Loosen the unit’s top panel screws near the top edge 

of the access panel. The access panel was designed to be 

captured underneath the top panel.)

2. Slide the first filter between both guide channels of filter 

rack and allow the filter to drop easily into place.

3. Verify the bottom of the filter is within the channels of the 

rack.

4. Slide the 2nd filter between both guide channels of filter 

rack.

5. Verify the bottom of the filter is within the channels of the 

rack.

6. Replace access cover by sliding the top edge of panel 

under the lip of the unit’s top panel. Secure access panel 

by replacing the screws.

Summary of Contents for R8GE Series

Page 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflamma...

Page 2: ...P Propane Gas Conversion 15 START UP ADJUSTMENTS 16 Pre Start Check List 16 Start Up Procedure 16 Air Circulation 16 System Cooling 16 System Heating 16 Verifying Adjusting Temperature Rise 16 Verifyi...

Page 3: ...brancher S assurer de les raccorder correctement S assurer que l appareil fonctionne ad quatement apr s l entretien WARNING TheseunitsarefullychargedwithR 410Arefrigerant andreadyforinstallation When...

Page 4: ...d the air vent intake terminal See page 8 Combustionproductsmustbedischargedoutdoors Connect this unit to an approved vent system only as specified on page 8 Never test for gas leaks with an open flam...

Page 5: ...nt Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructions D gaugement conforme aux codes d installation locaux aux...

Page 6: ...s suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapessuivantesdoivent tresuivi...

Page 7: ...als Carbon tetrachloride Halogen type refrigerants Cleaning solvents Cements glues paint removers varnishes etc Hydrochloric acid Masonry acid washing materials Plumbing Stack Venting Requirements Thi...

Page 8: ...ing operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under norma...

Page 9: ...tbelocatedaccordingtolocalbuilding codes or ordinances and these requirements The roof must be capable of handling the weight of the unit For unit weights see Table 9 page 21 Reinforce the roof if nec...

Page 10: ...ove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Remo...

Page 11: ...iring methods must be acceptable to authority having jurisdiction Useonlycopperwireforthelinevoltagepowersupplytothis unit See Table 4 page 12 Use proper code agency listed conduit and a conduit conne...

Page 12: ...225 110 Table 5 Thermostat Wire Gauge Table 3 Electrical Data MODEL NUMBER HEATING INPUT BTUH NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAX...

Page 13: ...lating blower motor has started Set the heat anticipator according to the thermostat manufacturer s instructions for heat anticipator settings Blower Speed The blower speed is preset at the factory fo...

Page 14: ...tbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases GAS SUPPLY PIPING WARNING FIRE OR...

Page 15: ...e carbon monoxide poisoning personal injury or death Conversion of this equipment to LP Propane gas must be made by qualified service personnel using approved factory parts Conversion to LP can be acc...

Page 16: ...andverifythecompressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for any unusual noises If unusua...

Page 17: ...operates for more thanfourminuteswithnoreturnair setthethermostatbelow room temperature shut off power to the unit and replace the over temperature limit control Verifying Burner Operation WARNING Un...

Page 18: ...ignition the furnace control is locked and the red LED will blink 4 times repetitively The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out Otherwise t...

Page 19: ...e unit 4 Turn the gas control knob to the OFF position See Figure 10 page 24 for gas valve shut off instructions 5 Disconnect the wires from the gas valve ignitor and flame sensor CAUTION Use care whe...

Page 20: ...ustion blower will continue to operate if the flame roll out control opens Flame Sensor Proves that flame has carried over from the ignitor to the right most burner If no flame is sensed the unit will...

Page 21: ...al Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 R8GE Dimensions Table 9 Center of Gravity Unit Shipping Weights Model Numb...

Page 22: ...62 1113 66 T3 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T4 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T5 2015 37 1970 37 1915 39 1870 39 1805 41 1740 42 168...

Page 23: ...E REVOLUTION SECONDS CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 1...

Page 24: ...utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Nejamaisutiliserd outils S iln estpaspo...

Page 25: ...SE FLAME OR GAS RELAY SHORTED PRESURE SWITCH STUCK OPEN WITH INDUCER ON PRESURE SWITCH STUCK CLOSED WITH INDUCER OFF WIRING DIAGRAM FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 10076210 05 15 FLAME ST...

Page 26: ...NGE BLUE RED GREEN YELLOW RED RED ORANGE WHITE WHITE BLUE YELLOW BLACK GREY GREEN BLACK BLACK GREEN WHITE YELLOW RED WHITE BLACK YELLOW 460 Volt Three Phase 60Hz 3 If any of the original wire as suppl...

Page 27: ...EFRIGERANT WHEN BELOW CURVE R8GE X36C X48C X60C Charging Chart Cooling Figure 13 Charging Chart for 3 Ton Units 3 5 TON MODELS 4 TON MODEL 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 5...

Page 28: ...Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity...

Reviews: