background image

5

GENERAL INFORMATION

The R8GE Single Package Gas Heating / Electric Cooling Unit 

is designed only for outdoor rooftop or ground level installations 

and can be readily connected to the high static duct system of 

a home. This unit has been tested for capacity and efficiency 

in accordance with AHRI Standards and will provide many 

years of safe and dependable comfort, providing it is properly 

installed and maintained. With regular maintenance, this unit 

will operate satisfactorily year after year. Abuse, improper 

use, and/or improper maintenance can shorten the life of the 

appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment 

failure, it is recommended that periodic maintenance be 

performed on this unit. The ability to properly perform 

maintenance on this equipment requires certain tools and 

mechanical skills.

Before you install this unit

 The cooling load of the area to be conditioned must be 

calculated and a system of the proper capacity selected. It is 

recommended that the area to be conditioned be completely 

insulated and vapor sealed.

 Check the electrical supply and verify the power supply is 

adequate for unit operation. Consideration should be given 

to availability of electric power, service access, noise, and 

shade. If there is any question concerning the power supply, 

contact the local power company.

 All units are securely packed at the time of shipment and 

upon arrival should be carefully inspected for damage prior 

to installing the equipment at the job site. Verify coil fins are 

straight. Claims for damage (apparent or concealed) should 

be filed immediately with the carrier.

 Survey the job site to determine the best location for 

mounting the outdoor unit. Choose an appropriate location 

that minimizes the length of the supply and return air ducts.

 Please consult your dealer for maintenance information 

and availability of maintenance contracts. Please read all 

instructions before installing the unit.

Locating the Equipment

•  Clearance in accordance with local installation codes, the 

requirements of the gas supplier and the manufacturer’s 

installation instructions.

•  Dégaugement conforme aux codes d’installation locaux, 

aux exigences du fournisseur de gaz et aux instructions 

d’installation du fabricant.

•  A clearance of at least 36 inches from the blower access 

panel and from the louvered control access panel is 

recommended for servicing and maintenance. 

Where 

accessibility to combustibles clearances are greater 

than minimum clearances, accessibility clearances 

must take preference.

•  Select a solid, level position, preferably on a concrete slab, 

slightly above the grade level, and parallel to the home. 

DO 

NOT PLACE UNIT UNDER THE HOME.

•  Overhead obstructions, poorly ventilated areas, and areas 

subject to accumulation of debris should be avoided. Do not 

place the unit in a confined space or recessed area where 

discharge air from the unit to re-circulate into the condenser 

air inlet, through the coil.

•  Sufficient clearance for unobstructed airflow through the 

louvered control access panel and outdoor coil must be 

maintained in order to achieve rated performance. See 

Figure 1

 for minimum clearances to obstructions.

•  The hot condenser air must be discharged up and away from 

the home, and if possible, in a direction with the prevailing 

wind.

•  If practical, place the air conditioner and its ducts in an area 

where they will be shaded from the afternoon sun, when 

the heat load is greatest.

Heating Load

This unit should be sized to provide the design heating 

load requirement. Heating load estimates can be made 

using approved methods available from Air Conditioning 

Contractors of America (Manual J); American Society of 

Heating, Refrigerating, and Air Conditioning Engineers; or other 

approved engineering methods. For installations above 2,000 

ft., the unit should have a sea level input rating large enough 

that it will meet the heating load after deration for altitude.

Figure 1. Clearance Requirements

Minimum Required 

Clearances to Combustibles

36"

36"

36"

TOP OF UNIT

TO

 BE

UNOBSTR

UCTED

See Note 1

See Note 2

NOTE 1:

 6” When coil is present on duct side.

NOTE 2:

 1” When no coil is present on duct side.

Summary of Contents for R8GE Series

Page 1: ...call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Nepasentreposerniutiliserdel essencenid autres vapeursouliquidesinflamma...

Page 2: ...P Propane Gas Conversion 15 START UP ADJUSTMENTS 16 Pre Start Check List 16 Start Up Procedure 16 Air Circulation 16 System Cooling 16 System Heating 16 Verifying Adjusting Temperature Rise 16 Verifyi...

Page 3: ...brancher S assurer de les raccorder correctement S assurer que l appareil fonctionne ad quatement apr s l entretien WARNING TheseunitsarefullychargedwithR 410Arefrigerant andreadyforinstallation When...

Page 4: ...d the air vent intake terminal See page 8 Combustionproductsmustbedischargedoutdoors Connect this unit to an approved vent system only as specified on page 8 Never test for gas leaks with an open flam...

Page 5: ...nt Clearance in accordance with local installation codes the requirements of the gas supplier and the manufacturer s installation instructions D gaugement conforme aux codes d installation locaux aux...

Page 6: ...s suivies pour chacun des appareils raccord s au syst me de ventilationaumomentdesamiseenmarche celapeut entra ner une intoxication au monoxyde de carbone ou la mort Les tapessuivantesdoivent tresuivi...

Page 7: ...als Carbon tetrachloride Halogen type refrigerants Cleaning solvents Cements glues paint removers varnishes etc Hydrochloric acid Masonry acid washing materials Plumbing Stack Venting Requirements Thi...

Page 8: ...ing operation If a combination of indoor and outdoor air is used the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under norma...

Page 9: ...tbelocatedaccordingtolocalbuilding codes or ordinances and these requirements The roof must be capable of handling the weight of the unit For unit weights see Table 9 page 21 Reinforce the roof if nec...

Page 10: ...ove access panel screws from return air panel Hint Loosen the unit s top panel screws near the top edge of the access panel The access panel was designed to be captured underneath the top panel 2 Remo...

Page 11: ...iring methods must be acceptable to authority having jurisdiction Useonlycopperwireforthelinevoltagepowersupplytothis unit See Table 4 page 12 Use proper code agency listed conduit and a conduit conne...

Page 12: ...225 110 Table 5 Thermostat Wire Gauge Table 3 Electrical Data MODEL NUMBER HEATING INPUT BTUH NOMINAL ELECTRICAL SUPPLY VOLTAGE RANGE COMPRESSOR FAN AMPS BLOWER MOTOR AMPS MINIMUM CIRCUIT AMPACITY MAX...

Page 13: ...lating blower motor has started Set the heat anticipator according to the thermostat manufacturer s instructions for heat anticipator settings Blower Speed The blower speed is preset at the factory fo...

Page 14: ...tbrush If any bubbling is observed the connection is not sealed adequately and must be retightened Repeat the tightening and soap check process until bubbling ceases GAS SUPPLY PIPING WARNING FIRE OR...

Page 15: ...e carbon monoxide poisoning personal injury or death Conversion of this equipment to LP Propane gas must be made by qualified service personnel using approved factory parts Conversion to LP can be acc...

Page 16: ...andverifythecompressor fan and indoor blower energize 2 Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature Listen for any unusual noises If unusua...

Page 17: ...operates for more thanfourminuteswithnoreturnair setthethermostatbelow room temperature shut off power to the unit and replace the over temperature limit control Verifying Burner Operation WARNING Un...

Page 18: ...ignition the furnace control is locked and the red LED will blink 4 times repetitively The thermostat must be opened for at least ten seconds to reset the furnace control after a lock out Otherwise t...

Page 19: ...e unit 4 Turn the gas control knob to the OFF position See Figure 10 page 24 for gas valve shut off instructions 5 Disconnect the wires from the gas valve ignitor and flame sensor CAUTION Use care whe...

Page 20: ...ustion blower will continue to operate if the flame roll out control opens Flame Sensor Proves that flame has carried over from the ignitor to the right most burner If no flame is sensed the unit will...

Page 21: ...al Supply Duct Opening Horizontal Return Duct Opening 4 0 1 75 9 75 24 75 16 0 Condensing Coil 13 5 16 0 16 0 C 13 5 Figure 9 R8GE Dimensions Table 9 Center of Gravity Unit Shipping Weights Model Numb...

Page 22: ...62 1113 66 T3 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T4 1788 41 1740 42 1692 44 1633 45 1574 47 1511 49 1449 51 1389 53 T5 2015 37 1970 37 1915 39 1870 39 1805 41 1740 42 168...

Page 23: ...E REVOLUTION SECONDS CUBIC FEET PER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 1...

Page 24: ...utili sant le t l phone d un voisin A d faut de la compagnie du gaz avertir le service des pompiers C Enfoncer ou faire tourner le robinet gaz la main seulement Nejamaisutiliserd outils S iln estpaspo...

Page 25: ...SE FLAME OR GAS RELAY SHORTED PRESURE SWITCH STUCK OPEN WITH INDUCER ON PRESURE SWITCH STUCK CLOSED WITH INDUCER OFF WIRING DIAGRAM FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE 10076210 05 15 FLAME ST...

Page 26: ...NGE BLUE RED GREEN YELLOW RED RED ORANGE WHITE WHITE BLUE YELLOW BLACK GREY GREEN BLACK BLACK GREEN WHITE YELLOW RED WHITE BLACK YELLOW 460 Volt Three Phase 60Hz 3 If any of the original wire as suppl...

Page 27: ...EFRIGERANT WHEN BELOW CURVE R8GE X36C X48C X60C Charging Chart Cooling Figure 13 Charging Chart for 3 Ton Units 3 5 TON MODELS 4 TON MODEL 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 5...

Page 28: ...Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO ELECTRICAL SYSTEM Electrical connections tight YES NO Line voltage polarity...

Reviews: