29
P6SP-120(C/D)a & Q6SP-120(C/D)a
Factory Standard: 1.5Hp Horizontal Performance Chart
‡ Indicates Factory Sheave Setting for Pre-configured Units
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open ‡
3
Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open
5
Turns
Open
5.5
Turns
Open
6
Turns
Open
0.1
CFM
4425
4303
4157
4011
3878
3745
RPM
688
671
653
635
617
599
kW
1.44
1.33
1.23
1.12
1.04
0.95
0.2
CFM
4366
4227
4087
3951
3815
3665
3515
RPM
707
690
672
655
637
619
601
kW
1.48
1.36
1.25
1.15
1.05
0.97
0.88
0.3
CFM
4278
4137
3994
3850
3694
3537
3369
3201
RPM
725
709
692
674
656
638
620
602
kW
1.50
1.39
1.28
1.17
1.07
0.98
0.89
0.80
0.4
CFM
4198
4061
3923
3763
3602
3425
3248
3071
RPM
743
727
711
694
676
658
640
623
kW
1.52
1.41
1.30
1.19
1.09
0.99
0.89
0.81
0.5
CFM
3969
3816
3662
3490
3318
3127
RPM
746
729
712
695
677
660
kW
1.44
1.32
1.20
1.10
0.99
0.89
0.6
CFM
3851
3719
3543
3366
3181
2996
RPM
764
749
732
714
698
681
kW
1.44
1.33
1.22
1.11
1.00
0.90
0.7
CFM
3749
3594
3438
3232
3026
RPM
781
767
752
734
716
kW
1.44
1.33
1.22
1.11
1.00
0.8
CFM
3614
3487
3298
3109
RPM
795
785
771
756
kW
1.44
1.34
1.22
1.10
0.9
CFM
3515
3352
3184
2946
RPM
813
801
789
773
kW
1.43
1.32
1.21
1.09
1.0
CFM
3218
2993
RPM
816
805
kW
1.31
1.18
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits
Table 10. Blower Performance for P6SP-120(C,D)a & Q6SP-120(C,D)a Series
(10 Ton Horizontal Models Only)