background image

9

Blower Speed

The blower speed is preset at the factory for an external 

static pressure of 0.2-0.3 in-Wg. For optimum system 

performance and comfort, it may be necessary to change 

the factory set speed. Refer to Blower Performance Data 

(Tables 5 - 10, pages 24 - 29) for the allowable operating 

range and adjustments.

 WARNING:

To avoid personal injury or property damage, 
make certain that the motor leads cannot 
come into contact with any uninsulated metal 
components of the unit.

To change the blower speed:
1.  Disconnect all electrical power to the unit and remove 

the blower access panel. 

2.  Loosen the motor tension bars to allow removal of the 

blower belt from the motor sheave.

3.  Loosen top set screw on motor sheave and turn 

clockwise to close (increases blower speed), or 

counterclockwise to open (decreases blower speed).

4.  Replace belt on pulleys and position motor mounting 

plate to correct position for proper belt tension.

5.  Tighten tension bar bolts.

Check all factory wiring per the unit wiring diagram and 

inspect the factory wiring connections to be sure none 

loosened during shipping or installation.

STARTUP & ADJUSTMENTS

Pre-Start Check List

• 

Verify that the unit is level to allow proper condensate 

drainage.

• 

Verify that there is free airflow to and from the outdoor 

coil and that all clearance requirements are met.

• 

Verify that the ductwork is sealed to prevent air leakage. 

• 

Verify that the line voltage power leads are securely 

connected and the unit is properly grounded.

•   Verify that low voltage wires are securely connected 

to correct leads in the low voltage area of the control 
box.

• 

Verify that all exterior panels are replaced and securely 

fastened.

• 

Verify that the outdoor fan turns freely.

• 

Verify that the power supply branch circuit overcurrent 

protection is sized properly.

• 

Verify  that  the  thermostat  is  wired  correctly.  The 

thermostat function switch should be set to 

Off

 and 

the thermostat fan switch should be set to 

Auto

.

Start-Up Procedure

 WARNING:

The unit is equipped with crankcase heaters. 
Allow 24 hours prior to continuing the start up 
procedures to allow for heating of the refrigerant 
compressor crankcase. Failure to comply may 
result in damage and could cause premature 
failure of the system. This warning should be 
followed at initial start up and any time the 
power has been removed for 12 hours or longer.

•  Check unit for return air filters and condensate trap.

•  Check all electrical wiring for loose connections and 

tighten as required.

•  Close all electrical disconnects to energize the system.

Air Circulation

Leave the thermostat system switch set to 

Off

 and set 

the thermostat fan switch to 

On

. The blower motor should 

run continuously. Check for air delivery at the register(s). 

Ensure that there are no obstructions at the registers or 

in the ductwork. Set thermostat fan switch to 

Auto

, the 

blower will shut down immediately. 

NOTE:

 If blower is 

turning opposite of arrow direction, shut off main power to 

the unit and switch any two field wires at the disconnect. 

DO NOT 

alter unit wiring.

System Cooling

1. Set the thermostat system switch to 

Cool

 and the 

thermostat fan switch to 

Auto

. Lower the thermostat 

temperature switch below room temperature and 

observe that the blower, both compressors and fan(s)

energize. Check that air cooler than room temperature is 

being discharged at the register. Ensure unit refrigerant 

pressures are in order. Blower should be turning in 

direction indicated by arrow. 

NOTE:

 If refrigerant 

pressures are abnormal and blower is rotating in the 

opposite direction of the arrow, shut off main power to 

the unit and switch any two field wires at the disconnect. 

Ensure proper rotation of both compressors. 

DO NOT

 

alter unit wiring. Listen for any unusual noises. Locate 

the source and correct as needed.

2. After allowing the unit to run for several minutes, set 

the temperature selector above room temperature, 

verify that the fan, blower, and compressors cycle off 

with the thermostat.

System Heating - Field Installed Electric Heat

This packaged air conditioner is designed to allow an 

optional electric heat kit to be field installed as required 

by the building’s particular heating load. The options 

available for each unit are shown in the heater kit installation 

instructions or unit technical service literature. Install the 

heater kits as directed by the instruction sheet that comes 

as part of the heater kit. Follow all cautions and warnings 

as directed. Use only NORDYNE manufactured heater kits.

Summary of Contents for P6SP

Page 1: ...deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper...

Page 2: ...a Multi Supply 20 Figure 13 Wiring Diag 072 090 120 Series 21 Figure 14 Ladder Diag 072 090 120 Series 22 Blower Performance Tables 23 Table 4 P6SP Alt Accessory Blower Drives 23 Table 5 P6SP 072 C D...

Page 3: ...place combustible materials including gasoline and any other flammable vapors and liquids in the vicinity of the unit WARNING PROPOSITION 65 WARNING This product contains fiberglass wool a product kno...

Page 4: ...of gravity Refer to Physical Data info pages 13 18 for center of gravity locations All panels must be securely in place during rigging and hoisting Roof Curb Condensate Drain 3 Min Figure 2 Condensate...

Page 5: ...or downflow applications never drill or punch holes in unit base Leakage may occur if unit bottom pan is punctured If any brand other than a NORDYNE Roof Curb is to be used the frame support must be c...

Page 6: ...talled in accordance with all applicablelocalcodesandthestandardsoftheNational Fire Protection Association Standard for Installation of Air Conditioning Systems NFPA 90A Design the ductwork according...

Page 7: ...ircuit containing the correct fuse or circuit breaker for the unit IMPORTANT NOTE An electrical disconnect must be installed readily accessible from and located within sight of the unit See unit data...

Page 8: ...ide of the control access panel and in Figures 13 16 pages 21 22 4 Secure the subbase or thermostat to the wall using screws provided with the thermostat 5 Install the correct thermostat housing to su...

Page 9: ...sor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should be followed at initial start up and any time the powerhasbeenremovedfor12hourso...

Page 10: ...ower mode 1 On a call for fan operation the thermostat applies 24 Vac directly to the blower contactor 2 The circulating blower is energized immediately Heating mode 1 On a call for heat the thermosta...

Page 11: ...mpartment The blower compartment should be cleaned monthly during the heating and cooling seasons to remove any dirt and lint that may have accumulated in the compartment or on the blower and motor Bu...

Page 12: ...eed for Removal with Curb Knockout for Bottom Power Entry Control Wiring Entry Power Wiring Entry 115v G F C I Convenience Outlet Factory or Field installed option Wiring supplied in field Condenser C...

Page 13: ...31 8 30 1 2 775 16 1 2 419 30 1 2 775 16 1 2 419 A Corner D Corner C Corner A Corner B B 30 762 16 1 2 419 30 762 16 1 2 419 7 178 7 1 4 184 Filter Access Horizontal Duct connections for optional acc...

Page 14: ...t mounting location Rating Label 15 3 8 390 AIR AIR Optional Economizer Hoods bottom pan top View Figure 10 P6SP 072 Series Continued physical data continued Dimensions shown in inches mm 5 3 4 146 16...

Page 15: ...Access Optional Hail Guard Hood front View 43 1 2 1403 30 762 4 102 4 102 7 1 4 184 16 1 2 419 7 178 30 762 16 1 2 419 Filter Access Horz Return Air Opening Condenser Coil Horizontal Discharge Air Ope...

Page 16: ...n top View 5 3 4 146 16 1 2 419 30 1 2 775 Discharge Air Opening 7 178 7 178 Return Air Opening 16 1 2 419 30 1 2 775 Power Entry 8 3 4 222 62 1575 101 1 4 2572 condenser end Airflow Airflow Compresso...

Page 17: ...te Drain Field Wiring Electric Element Access 2 51 4 102 Recommended Unit Disconnect Location 16 1 2 30 762 419 16 1 2 7 1 4 4 102 30 762 184 419 178 7 419 16 1 2 Filter Access Coil Condenser Heat Exc...

Page 18: ...pping Weight Center of Gravity Inches mm Corner Weights Unit Height A B C D Horizontal Duct Applications Vertical Duct Applications Lbs Kg Lbs Kg A B Lbs Kg Lbs Kg Lbs Kg Lbs Kg P6SP 072 C D 845 384 9...

Page 19: ...090Ca 208 230 V Factory Std 2 ea 13 1 83 1 2 3 1 5 4 4 4 2 35 2 39 39 50 50 090Da 460 V 2 ea 6 1 41 1 2 2 1 16 7 19 20 120Ca 208 230 V Factory Std 2 ea 16 0 110 2 3 1 5 4 4 4 2 41 0 45 45 60 60 120Da...

Page 20: ...81 92 97 110 60 60 60 60 90 100 100 110 120Da 460 V 22 30 46 55 25 30 50 60 Medium High Static Drive Electrical Data 072C 208 230 V 920609 32 33 51 58 81 92 n a 50 45 60 60 90 100 n a 072D 460 V 9205...

Page 21: ...2 L3 T1 T2 T3 BLWR CON COM 5 5 S2 CCH S2 FS S2 LP S2 HP YE BR BR BR BR L1 L2 L3 T1 T2 T3 L1 L2 L3 T1 T2 T3 COMP 2 T2 T3 T1 BK BK BK BK BR BR S2 COMP CON S1 COMP CON L3 L1 L1 L2 L2 L3 L3 ECONOMIZER PLU...

Page 22: ...2 L3 GND 24V Common 24V Hot Compressor 1 T2 T3 T1 CC2 Compressor 2 T2 T1 T3 CC1 Aux Switch N C CC2 Aux Switch N C CC1 CCH1 CCH2 IBC OFC Y1 Factory Jumper CC2 CC1 LVT C 24V COM IBC Aux Switch N O Field...

Page 23: ...listed below for the high static drive kits The factory standard drive installed in these units has been set to deliver 400 Cfm ton at an External Static Pressure ESP of 0 25 0 30 in Wg Tables 5 10 sh...

Page 24: ...8 2322 2181 2040 1870 RPM 897 876 855 831 807 780 kW 0 96 0 88 0 80 0 71 0 62 0 54 0 6 CFM 2395 2255 2115 1960 1805 RPM 901 880 858 834 809 kW 0 87 0 79 0 71 0 63 0 55 0 7 CFM 2509 2362 2214 2042 1870...

Page 25: ...1 1904 RPM 836 812 788 760 731 kW 0 88 0 77 0 67 0 60 0 54 0 6 CFM 2687 2518 2349 2177 2005 RPM 885 862 838 815 791 kW 0 98 0 88 0 79 0 69 0 59 0 7 CFM 2460 2276 2092 RPM 889 865 841 kW 0 90 0 80 0 70...

Page 26: ...9 3239 3115 2991 2846 2700 2549 2398 2257 RPM 990 972 950 928 904 881 857 833 813 kW 1 52 1 41 1 30 1 20 1 09 0 99 0 89 0 80 0 72 0 7 CFM 3294 3184 3074 2942 2810 2652 2493 2316 RPM 1011 993 975 953 9...

Page 27: ...2 2919 2776 2616 2455 2282 RPM 986 966 947 928 904 879 856 833 809 kW 1 57 1 46 1 34 1 23 1 12 1 01 0 92 0 83 0 74 0 7 CFM 3360 3251 3142 3012 2881 2722 2563 2388 2212 RPM 1010 990 971 951 931 907 882...

Page 28: ...9 712 695 678 659 639 623 kW 1 51 1 39 1 27 1 17 1 08 0 99 0 91 0 81 0 5 CFM 3998 3871 3706 3540 3368 3196 3017 RPM 761 747 731 714 697 680 661 kW 1 51 1 42 1 30 1 18 1 09 0 99 0 90 0 6 CFM 4016 3903...

Page 29: ...1 RPM 743 727 711 694 676 658 640 623 kW 1 52 1 41 1 30 1 19 1 09 0 99 0 89 0 81 0 5 CFM 3969 3816 3662 3490 3318 3127 RPM 746 729 712 695 677 660 kW 1 44 1 32 1 20 1 10 0 99 0 89 0 6 CFM 3851 3719 35...

Page 30: ...over the range of operation Always reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit effic...

Page 31: ...ication Notes for use Add refrigerant when below curve Remove refrigerant when above curve 180 205 230 255 280 305 330 355 380 405 430 455 480 505 530 555 580 50 55 60 65 70 75 80 85 90 95 100 105 110...

Page 32: ...______ F Temperature Rise ___________ F INSTALLATION ADDRESS CITY_________________________ STATE_________________ UNIT MODEL _________________________________________ UNIT SERIAL _____________________...

Reviews: