background image

10

1. Set the thermostat to above room temperature. 

2. Verify that the compressor and outdoor fan motor are 

not energized and the electric heat is energized. 

3. After the unit has run for approximately five minutes, 

set the thermostat below room temperature and verify 

that the electric heat has de-energized.

 WARNING:

Uninsulated live components are exposed when 
control access panel is removed.

Verify Operation of Over-Temperature Limit Control

To verify operation of the over-temperature limit control, 

make sure that all access panels are in place and that 

there is power to the unit. Block the return airflow to the 

unit by installing a close-off plate in place of or upstream 

of the filter. Set the thermostat to a temperature above 

room temperature and verify the unit operates with the 

correct operating sequence (see Operating Sequence). 

The over-temperature limit control should function to turn 

off the electric strip heat within approximately four minutes 

NOTE:

 the exact time depending on the efficiency of the 

close-off in blocking the return air to the unit.

The circulating air blower should continue to run when 

the over-temperature limit control switch opens. Remove 

the close-off immediately after the over-temperature limit 

control opens. If the unit operates for more than four minutes 

with no return air, set the thermostat to a temperature 

below room temperature, shut off the power to the unit, 

and replace the over-temperature limit control.

OPERATING SEQUENCE

The operating sequences for the heating, cooling, and fan 

modes are described below. Refer to the wiring diagrams 

for the unit. See pages 21 - 22

Cooling mode

1.  On a call for cooling the thermostat closes, applying 

24 Vac to 

Y1

G

, and 

Y2

 if stage 2 cooling is required.

2. 

G

 applies 24VAC to the main circulating blower circuit.

3. 

Y1

 and 

Y2

 apply 24VAC through all safety switches 

Before energizing their respective contactors.

4.  When the thermostat is satisfied the contactors are 

De-energized.

5. The circulating blower motor is de-energized 

Immediately.

Blower mode

1. On a call for fan operation, the thermostat applies 24 

Vac directly to the blower contactor.

2. The circulating blower is energized immediately.

Heating mode

1. On a call for heat the thermostat closes, applying 24 

Vac to the 

W1

 terminal.

Unit Fails to Operate

If the unit does not operate properly in either the heating 

or cooling mode, be certain to check the following:

1.  The thermostat is operating properly.

UNIT MAINTENANCE

 WARNING:

To avoid risk of electrical shock, personal 
injury, or death, disconnect all electrical power 
to the unit before performing any maintenance 
or service. The unit may have more than one 
electrical supply.

 CAUTION:

Use care when removing parts from this unit. 
Personal injury can result from sharp metal 
edges present in all equipment of sheet metal 
construction.

 CAUTION:

Verify proper operation after servicing.

Refrigerant Charging

Packaged electric units are fully charged at the factory. 

The system refrigerant charge can be checked and 

adjusted through the service ports provided behind the 

compressor service panel. Use only gauge lines which 

have a “Schrader” depression device present to actuate 

the valve. Draw a vacuum on gauge lines to remove 

air or moisture before attaching them to the service 

ports on the unit. Refrigerant charging must be done by 

qualified personnel familiar with safe and environmentally 

responsible refrigerant handling procedures. See Unit 

Rating Plate for proper amount of charge. See page 30.

 WARNING:

The units are shipped fully charged and ready 
for installation. When a system is installed 
according to these instructions, no refrigerant 
charging is required. If repairs make it necessary 
for evacuation and charging, it should only be 
done by qualified, trained personnel thoroughly 
familiar with this equipment. Some local codes 
require licensed installation/service personnel 
to service this type of equipment. Under no 
circumstances should the owner attempt to 
install and/or service this equipment. Failure 
to comply with this warning could result in 
property damage, personal injury, or death.

2.  Electrical power to the unit is turned on.

3.  All safety switches are closed.

4.  The service doors are in place.

5.  Transformer circuit breaker is reset.

Summary of Contents for P6SP

Page 1: ...deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper...

Page 2: ...a Multi Supply 20 Figure 13 Wiring Diag 072 090 120 Series 21 Figure 14 Ladder Diag 072 090 120 Series 22 Blower Performance Tables 23 Table 4 P6SP Alt Accessory Blower Drives 23 Table 5 P6SP 072 C D...

Page 3: ...place combustible materials including gasoline and any other flammable vapors and liquids in the vicinity of the unit WARNING PROPOSITION 65 WARNING This product contains fiberglass wool a product kno...

Page 4: ...of gravity Refer to Physical Data info pages 13 18 for center of gravity locations All panels must be securely in place during rigging and hoisting Roof Curb Condensate Drain 3 Min Figure 2 Condensate...

Page 5: ...or downflow applications never drill or punch holes in unit base Leakage may occur if unit bottom pan is punctured If any brand other than a NORDYNE Roof Curb is to be used the frame support must be c...

Page 6: ...talled in accordance with all applicablelocalcodesandthestandardsoftheNational Fire Protection Association Standard for Installation of Air Conditioning Systems NFPA 90A Design the ductwork according...

Page 7: ...ircuit containing the correct fuse or circuit breaker for the unit IMPORTANT NOTE An electrical disconnect must be installed readily accessible from and located within sight of the unit See unit data...

Page 8: ...ide of the control access panel and in Figures 13 16 pages 21 22 4 Secure the subbase or thermostat to the wall using screws provided with the thermostat 5 Install the correct thermostat housing to su...

Page 9: ...sor crankcase Failure to comply may result in damage and could cause premature failure of the system This warning should be followed at initial start up and any time the powerhasbeenremovedfor12hourso...

Page 10: ...ower mode 1 On a call for fan operation the thermostat applies 24 Vac directly to the blower contactor 2 The circulating blower is energized immediately Heating mode 1 On a call for heat the thermosta...

Page 11: ...mpartment The blower compartment should be cleaned monthly during the heating and cooling seasons to remove any dirt and lint that may have accumulated in the compartment or on the blower and motor Bu...

Page 12: ...eed for Removal with Curb Knockout for Bottom Power Entry Control Wiring Entry Power Wiring Entry 115v G F C I Convenience Outlet Factory or Field installed option Wiring supplied in field Condenser C...

Page 13: ...31 8 30 1 2 775 16 1 2 419 30 1 2 775 16 1 2 419 A Corner D Corner C Corner A Corner B B 30 762 16 1 2 419 30 762 16 1 2 419 7 178 7 1 4 184 Filter Access Horizontal Duct connections for optional acc...

Page 14: ...t mounting location Rating Label 15 3 8 390 AIR AIR Optional Economizer Hoods bottom pan top View Figure 10 P6SP 072 Series Continued physical data continued Dimensions shown in inches mm 5 3 4 146 16...

Page 15: ...Access Optional Hail Guard Hood front View 43 1 2 1403 30 762 4 102 4 102 7 1 4 184 16 1 2 419 7 178 30 762 16 1 2 419 Filter Access Horz Return Air Opening Condenser Coil Horizontal Discharge Air Ope...

Page 16: ...n top View 5 3 4 146 16 1 2 419 30 1 2 775 Discharge Air Opening 7 178 7 178 Return Air Opening 16 1 2 419 30 1 2 775 Power Entry 8 3 4 222 62 1575 101 1 4 2572 condenser end Airflow Airflow Compresso...

Page 17: ...te Drain Field Wiring Electric Element Access 2 51 4 102 Recommended Unit Disconnect Location 16 1 2 30 762 419 16 1 2 7 1 4 4 102 30 762 184 419 178 7 419 16 1 2 Filter Access Coil Condenser Heat Exc...

Page 18: ...pping Weight Center of Gravity Inches mm Corner Weights Unit Height A B C D Horizontal Duct Applications Vertical Duct Applications Lbs Kg Lbs Kg A B Lbs Kg Lbs Kg Lbs Kg Lbs Kg P6SP 072 C D 845 384 9...

Page 19: ...090Ca 208 230 V Factory Std 2 ea 13 1 83 1 2 3 1 5 4 4 4 2 35 2 39 39 50 50 090Da 460 V 2 ea 6 1 41 1 2 2 1 16 7 19 20 120Ca 208 230 V Factory Std 2 ea 16 0 110 2 3 1 5 4 4 4 2 41 0 45 45 60 60 120Da...

Page 20: ...81 92 97 110 60 60 60 60 90 100 100 110 120Da 460 V 22 30 46 55 25 30 50 60 Medium High Static Drive Electrical Data 072C 208 230 V 920609 32 33 51 58 81 92 n a 50 45 60 60 90 100 n a 072D 460 V 9205...

Page 21: ...2 L3 T1 T2 T3 BLWR CON COM 5 5 S2 CCH S2 FS S2 LP S2 HP YE BR BR BR BR L1 L2 L3 T1 T2 T3 L1 L2 L3 T1 T2 T3 COMP 2 T2 T3 T1 BK BK BK BK BR BR S2 COMP CON S1 COMP CON L3 L1 L1 L2 L2 L3 L3 ECONOMIZER PLU...

Page 22: ...2 L3 GND 24V Common 24V Hot Compressor 1 T2 T3 T1 CC2 Compressor 2 T2 T1 T3 CC1 Aux Switch N C CC2 Aux Switch N C CC1 CCH1 CCH2 IBC OFC Y1 Factory Jumper CC2 CC1 LVT C 24V COM IBC Aux Switch N O Field...

Page 23: ...listed below for the high static drive kits The factory standard drive installed in these units has been set to deliver 400 Cfm ton at an External Static Pressure ESP of 0 25 0 30 in Wg Tables 5 10 sh...

Page 24: ...8 2322 2181 2040 1870 RPM 897 876 855 831 807 780 kW 0 96 0 88 0 80 0 71 0 62 0 54 0 6 CFM 2395 2255 2115 1960 1805 RPM 901 880 858 834 809 kW 0 87 0 79 0 71 0 63 0 55 0 7 CFM 2509 2362 2214 2042 1870...

Page 25: ...1 1904 RPM 836 812 788 760 731 kW 0 88 0 77 0 67 0 60 0 54 0 6 CFM 2687 2518 2349 2177 2005 RPM 885 862 838 815 791 kW 0 98 0 88 0 79 0 69 0 59 0 7 CFM 2460 2276 2092 RPM 889 865 841 kW 0 90 0 80 0 70...

Page 26: ...9 3239 3115 2991 2846 2700 2549 2398 2257 RPM 990 972 950 928 904 881 857 833 813 kW 1 52 1 41 1 30 1 20 1 09 0 99 0 89 0 80 0 72 0 7 CFM 3294 3184 3074 2942 2810 2652 2493 2316 RPM 1011 993 975 953 9...

Page 27: ...2 2919 2776 2616 2455 2282 RPM 986 966 947 928 904 879 856 833 809 kW 1 57 1 46 1 34 1 23 1 12 1 01 0 92 0 83 0 74 0 7 CFM 3360 3251 3142 3012 2881 2722 2563 2388 2212 RPM 1010 990 971 951 931 907 882...

Page 28: ...9 712 695 678 659 639 623 kW 1 51 1 39 1 27 1 17 1 08 0 99 0 91 0 81 0 5 CFM 3998 3871 3706 3540 3368 3196 3017 RPM 761 747 731 714 697 680 661 kW 1 51 1 42 1 30 1 18 1 09 0 99 0 90 0 6 CFM 4016 3903...

Page 29: ...1 RPM 743 727 711 694 676 658 640 623 kW 1 52 1 41 1 30 1 19 1 09 0 99 0 89 0 81 0 5 CFM 3969 3816 3662 3490 3318 3127 RPM 746 729 712 695 677 660 kW 1 44 1 32 1 20 1 10 0 99 0 89 0 6 CFM 3851 3719 35...

Page 30: ...over the range of operation Always reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit effic...

Page 31: ...ication Notes for use Add refrigerant when below curve Remove refrigerant when above curve 180 205 230 255 280 305 330 355 380 405 430 455 480 505 530 555 580 50 55 60 65 70 75 80 85 90 95 100 105 110...

Page 32: ...______ F Temperature Rise ___________ F INSTALLATION ADDRESS CITY_________________________ STATE_________________ UNIT MODEL _________________________________________ UNIT SERIAL _____________________...

Reviews: