26
P6SP-090(C/D)a
Factory Standard: 1.5Hp Downflow Performance Chart
‡ Indicates Factory Sheave Setting
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open ‡
5
Turns
Open
5.5
Turns
Open
6
Turns
Open
0.1
CFM
3620
3515
3400
3285
3187
3089
RPM
893
870
847
823
803
783
kW
1.47
1.35
1.25
1.15
1.06
0.98
0.2
CFM
3590
3477
3363
3248
3132
3031
2930
RPM
918
895
872
848
825
805
785
kW
1.50
1.39
1.28
1.18
1.08
1.00
0.92
0.3
CFM
3549
3441
3331
3220
3097
2973
2864
2755
RPM
941
920
897
873
850
827
807
786
kW
1.55
1.44
1.33
1.22
1.12
1.02
0.94
0.86
0.4
CFM
3532
3419
3306
3185
3063
2932
2800
2687
2574
RPM
965
944
923
899
876
853
830
809
788
kW
1.58
1.47
1.36
1.25
1.14
1.05
0.95
0.87
0.80
0.5
CFM
3382
3267
3152
3021
2889
2750
2611
2484
2357
RPM
968
947
925
902
878
855
832
811
790
kW
1.50
1.39
1.28
1.17
1.07
0.97
0.87
0.80
0.72
0.6
CFM
3339
3239
3115
2991
2846
2700
2549
2398
2257
RPM
990
972
950
928
904
881
857
833
813
kW
1.52
1.41
1.30
1.20
1.09
0.99
0.89
0.80
0.72
0.7
CFM
3294
3184
3074
2942
2810
2652
2493
2316
RPM
1011
993
975
953
930
907
884
859
kW
1.55
1.44
1.33
1.22
1.11
1.01
0.90
0.81
0.8
CFM
3136
3024
2911
2762
2613
2435
2257
RPM
1013
995
978
955
933
910
887
kW
1.45
1.35
1.24
1.13
1.03
0.92
0.81
0.9
CFM
3082
2979
2850
2720
2548
2376
RPM
1033
1016
998
980
958
935
kW
1.48
1.36
1.25
1.15
1.03
0.92
1.0
CFM
3012
2897
2789
2647
2505
2301
RPM
1054
1036
1019
1001
984
961
kW
1.48
1.38
1.26
1.15
1.04
0.93
1.1
CFM
2834
2718
2572
2407
2242
RPM
1058
1041
1024
1005
987
kW
1.36
1.27
1.16
1.05
0.93
1.2
CFM
2630
2485
2335
RPM
1061
1045
1028
kW
1.26
1.16
1.04
1.3
CFM
2405
2237
RPM
1064
1049
kW
1.14
1.04
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits
Table 7. Blower Performance for P6SP-090(C,D)a Series
(7.5 Ton Downflow Models Only)