P6SP-072(C/D)
Factory Standard: 1.5Hp Horizontal Performance Chart
‡ Indicates Factory Sheave Setting for Pre-configured Units
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Turn
Open
1
Turn
Open
1.5
Turns
Open ‡
2.0
Turns
Open
2.5
Turns
Open
3.0
Turns
Open
3.5
Turns
Open
4.0
Turns
Open
4.5
Turns
Open
5.0
Turns
Open
5.5
Turns
Open
6.0
Turns
Open
0.2
CFM
2665
RPM
727
kW
0.74
0.3
CFM
2720
2584
2447
RPM
781
755
729
kW
0.82
0.75
0.67
0.4
CFM
2654
2504
2346
2188
RPM
808
784
757
730
kW
0.85
0.74
0.67
0.60
0.5
CFM
2591
2425
2258
2081
1904
RPM
836
812
788
760
731
kW
0.88
0.77
0.67
0.60
0.54
0.6
CFM
2687
2518
2349
2177
2005
RPM
885
862
838
815
791
kW
0.98
0.88
0.79
0.69
0.59
0.7
CFM
2460
2276
2092
RPM
889
865
841
kW
0.90
0.80
0.70
0.8
CFM
2572
2383
2193
2007
1821
RPM
937
915
892
869
846
kW
1.04
0.93
0.82
0.73
0.63
0.9
CFM
2325
2137
1948
RPM
940
919
898
kW
0.93
0.82
0.72
1.0
CFM
RPM
kW
Values includes losses for: Unit Casing, 2” Disposable (Pleated) Filters & Dry Evaporator Coil
When utilized with H5HK Heater kits, not all operational points shown may be available for use. Refer to the H5HK Installation
Instructions to determine the minimum airflow requirements of the applicable heater assembly.
Deduct 250 Cfm for electric heater kits
Table 6. Blower Performance for P6SP-072(C,D) Series
(6 Ton Horizontal Models Only)