10-40
Page 34
2008-10-01
(7)
Factory mounted, full size, backlit, Liquid Crystal Display provides full operational
status. Display to include a keypad for user interface and adjustment of operational
parameters including:
(a)
Unit output (lbs/hr or kg/hr) 25 lbs/hr to full output.
(b)
Water level in the tank.
(c)
Modulating control demand status.
(d)
On/off control and safety (High limit, air proving) circuit status.
(e)
Actual room and/or duct RH, and humidity set point, when using transducer
input(s).
(f)
Controller configuration (Proportional band and integral) when using
transducer input(s).
(g)
Troubleshooting guide with scroll down menu.
(h)
Fault indication including date and time history.
(i) Maintenance
intervals.
(j)
Fill and drain status.
(k)
Drain/flush intervals and duration.
(l)
Date and time.
(m) Capacity
limitation.
(n)
72 hours drain enable/disable.
(o)
Control type configuration on/off or full modulation when demand signal(s), or
transducer input(s) are provided.
(p)
Up to 10 humidifiers, supplying one AHU or area, can be controlled in series
from one modulating humidity control system.
(q)
BACnet, LonWorks, or Johnson N2 capable to interface for monitoring and
control from a Building Management System (BMS/BAS).
(r)
Total Controller is Modbus native for (BMS/BAS) communication for remote
monitoring and control of humidifier.
(s)
Web base capable via the Internet for remote monitoring or control of
humidifier.
NOTE:
All operational parameters factory set to reduce field set-up time.
(8)
Standard of acceptance: NORTEC GSTC.
(9) Optional
accessories:
(a)
Refer to options schedule.
Summary of Contents for GS Series GSP Indoor
Page 1: ...1503540 C GS Series GSTC GSP Indoor GSTC Outdoor Engineering Manual ...
Page 7: ...2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 8: ...10 00 Page 1 2008 10 01 10 00 PRINCIPLE OF OPERATION ...
Page 10: ...10 00 Page 3 2008 10 01 Figure 1 GS Indoor Series Figure 2 GS Outdoor Series ...
Page 11: ...10 00 Page 4 2008 10 01 Figure 3 GSTC Key Pad Figure 4 GSP Key Pad ...
Page 13: ...10 00 Page 6 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...10 10 Page 7 2008 10 01 10 10 OPERATION ...
Page 17: ...10 10 Page 10 2008 10 01 Figure 3 Physical Dimensions GS Outdoor Humidifier ...
Page 21: ...10 10 Page 14 2008 10 01 Figure 4 GSTC GSP Indoor Clearance Figure 5 GSTC Outdoor Clearance ...
Page 23: ...10 10 Page 16 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...10 20 Page 17 2008 10 01 10 20 MAINTENANCE ...
Page 27: ...10 20 Page 20 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 28: ...10 30 Page 21 2008 10 01 10 30 OPTIONS ACCESSORIES ...
Page 35: ...10 30 Page 28 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...10 40 Page 29 2008 10 01 10 40 SPECIFICATION ...
Page 44: ...10 40 Page 37 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...