![Nortec GS Series GSP Indoor Engineer'S Manual Download Page 26](http://html1.mh-extra.com/html/nortec/gs-series-gsp-indoor/gs-series-gsp-indoor_engineers-manual_1705785026.webp)
10-20
Page 19
2008-10-01
maintenance a step further than RO and all the GS Series components are ready
for RO or DI water use as a standard.
(10) Contact your local Nortec representative for a quotation of a water treatment
system suited for your application.
2. PREVENTIVE MAINTENANCE
(1)
The installation manuals of the GS Series of Gas Steam humidifier come with a
complete Maintenance chart in order to guide internal personnel in cleaning and
monitoring activities. Like any other appliance the Gas-Steam humidifier requires
monitoring to ensure efficient operation throughout the life of the unit.
(2)
While in operation, the unit will blowdown scaled water through a drain pump
keeping control on the water concentration based on steam output. For longer
intervals between cleaning, the unit may be completely drained down to reduce the
mineral concentration and bring in new fresh water in the system.
(3)
The FTBD (Full Tank Blow Down) can be activated through the software or dip
switches based on:
(a)
Time of day setting. When the 25 - 400 hours interval (adjustable ) is reached
the unit will wait until the set time of day before activating the full tank
blowdown.
(b)
External trigger using 24Vac signal from the building management system to
the input terminal of the humidifier.
(4)
Following the full tank blowdown, the unit will refill and perform a float check.
Whenever possible, use this feature to reduce mineral accumulation in the system
and reduce the time required to clean the interior of the reservoir.
3. PRE-CLEANING SEQUENCE
(1)
When cleaning of the reservoir is required, use the tank pre-clean feature. This
pre-cleaning sequence will drain the full content of the unit, fill back-up, and re-
drain any residual scale that has fallen from the cold water refilling. This sequence
is not an alternative to cleaning the humidifier, it is meant to reduce the time
required to clean the tank.
(2)
Full Size Frontal Opening: Every GS Series Gas Steam Humidifier comes
complete with a full size frontal opening to allow bottom cleaning of the tank and
heat exchanger. This opening allows quick and easy cleaning without removing
the steam outlet of the unit.
Summary of Contents for GS Series GSP Indoor
Page 1: ...1503540 C GS Series GSTC GSP Indoor GSTC Outdoor Engineering Manual ...
Page 7: ...2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 8: ...10 00 Page 1 2008 10 01 10 00 PRINCIPLE OF OPERATION ...
Page 10: ...10 00 Page 3 2008 10 01 Figure 1 GS Indoor Series Figure 2 GS Outdoor Series ...
Page 11: ...10 00 Page 4 2008 10 01 Figure 3 GSTC Key Pad Figure 4 GSP Key Pad ...
Page 13: ...10 00 Page 6 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...10 10 Page 7 2008 10 01 10 10 OPERATION ...
Page 17: ...10 10 Page 10 2008 10 01 Figure 3 Physical Dimensions GS Outdoor Humidifier ...
Page 21: ...10 10 Page 14 2008 10 01 Figure 4 GSTC GSP Indoor Clearance Figure 5 GSTC Outdoor Clearance ...
Page 23: ...10 10 Page 16 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 24: ...10 20 Page 17 2008 10 01 10 20 MAINTENANCE ...
Page 27: ...10 20 Page 20 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 28: ...10 30 Page 21 2008 10 01 10 30 OPTIONS ACCESSORIES ...
Page 35: ...10 30 Page 28 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 36: ...10 40 Page 29 2008 10 01 10 40 SPECIFICATION ...
Page 44: ...10 40 Page 37 2008 10 01 THIS PAGE INTENTIONALLY LEFT BLANK ...