FD67 Profibus-DP Manual
87
8.3.5 FD67AICM120004
8.3.5.1 Identification
Compact module
Part. No
Process data
ID
Input
Output
Analogue input current M12
FD67AICM120004 4 words -
42
hex
43
hex
DD
hex
9A
hex
8.3.5.2 I/O data
8.3.5.2.1 Input data IDM
Word
0
1
2
3
Byte
0
1
2
3
4
5
6
7
Measured
value
Channel 0
Channel 1
Channel 2
Channel 3
8.3.5.2.2 Byte sequence High/Low - Motorola (standard setting)
Byte
Byte 0 (High-Byte)
Byte 1 (Low-Byte)
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Value
VZ
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
8.3.5.2.3 Byte sequence Low/High - Intel
Byte
Byte 0 (Low-Byte)
Byte 1 (High-Byte)
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Value
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
VZ
2
14
2
13
2
12
2
11
2
10
2
9
2
8
8.3.5.2.4 Representation of analogue values
Measured value
Measuring range
0..20 mA
binary
hexadecimal decimal
Area
Diagnosis
> 20 mA
0111 1111 1111 1111
7FFF
32767
Overshooting
yes
20 mA
10 mA
4 mA
0
0111 1111 1111 1111
0011 1111 1111 1111
0001 1001 1001 1001
0000 0000 0000 0000
7FFF
3FFF
1999
0000
32767
16383
6553
0
Nominal range -
< 0 mA
0000 0000 0000 0000
0000
0
Undershooting -
Measured value
Measuring range
4..20 mA
binary
hexadecimal decimal
Area
Diagnosis
>20 mA
0111 1111 1111 1111
7FFF
32767
Overshooting
ja
20 mA
10 mA
4 mA
0111 1111 1111 1111
0010 1111 1111 1010
0000 0000 0000 0000
7FFF
2FFA
0000
32767
12282
0
Nominal range -
< 4 mA
0000 0000 0000 0000
0000
0
Undershooting yes
17
17
„Line breakage“ < 2mA or „Lower threshold undershot“ < 4mA