FD67 Profibus-DP Manual
24
5.3.4.5 Manual assembling of a configuration string
♦
Fig. 5-1 : Configuration example
The modules are automatically addressed by the bus node in the order of connection : first all the
modules connected to socket 0 of the internal system connection, then all the modules connected to
socket 1 of the internal system connection and so on.
The configurations strings of the different modules can be found in chapter 5.3.2.
1. Bus
node
Module
Identification
FD67NDPM127804
01
hex
51
hex
2. I/O modules
Nb/Slot
Art.No
Internal system connection Identification
0
FD67DIOM121216 Socket 0
C2
hex
01
hex
01
hex
DD
hex
18
hex
1
FD67DIOM120008 Socket 2
C2
hex
01
hex
01
hex
DD
hex
23
hex
2
FD67DIOM080008 Socket 2
C2
hex
00
hex
00
hex
DD
hex
2D
hex
3
FD67AOVM120004 Socket 2
82
hex
43
hex
DD
hex
86
hex
4
FD67DIOM080008 Socket 3
C2
hex
00
hex
00
hex
DD
hex
2D
hex
5
FD67DIOM120016 Socket 3
C2
hex
01
hex
01
hex
DD
hex
19
hex
3. The configuration string (all values in hexadecimal notation) looks like this :
C2,01,01,DD,18 C2,01,01,DD,23 C2,00,00,DD,2D
82,43,DD,86
C2,00,00,DD,2D C2,01,01,DD,19
The configuration software generally supports a visual configuration, so you don't have to assemble the
configuration string yourself.
FD67DIOM121216
FD67DIOM120016
FD67DIOM080008
FD67AOVM120004
FD67DIOM080008
FD67DIOM120008
FD67NDPM127804