FD67 Profibus-DP Manual
8
0
8.3.2.2.4 Representation of analogue values
Measured value
Area
Diagnosis
Measuring range
0..10 V
binary
hexadecimal
decimal
>10 V
0111 1111 1111 1111
7FFF
32767
Overshooting
yes
10 V
5V
0,305mV
0
0111 1111 1111 1111
0011 1111 1111 1111
0000 0000 0000 0001
0000 0000 0000 0000
7FFF
3FFF
0001
0000
32767
16383
1
0
Nominal range -
< 0V
0000 0000 0000 0000
0000
0
Undershooting -
Measured value
Measuring range
+/-10 V
binary
hexadecimal
decimal
Area
Diagnosis
>10 V
0111 1111 1111 1111
7FFF
32767
Overshooting
yes
10 V
5V
0,305mV
0
0111 1111 1111 1111
0011 1111 1111 1111
0000 0000 0000 0001
0000 0000 0000 0000
7FFF
3FFF
0001
0000
32767
16383
1
0
Nominal range -
-0,305mV
-5V
-10V
1111 1111 1111 1111
1100 0000 0000 0001
1000 0000 0000 0000
FFFF
C000
8000
-1
-16384
-32768
Nominal range -
< -10V
1000 0000 0000 0000
8000
-32768
Undershooting yes
8.3.2.3 Parameter bytes
Byte
Signification
0
Settings channel 0
1
Reserved
2
3
Channel 0 : Delta
4
Settings channel 1
5
Reserved
6
7
Channel 1 : Delta
8
Settings channel 2
9
Reserved
10
11
Channel 2 : Delta
12
Settings channel 3
13
Reserved
14
15
Channel 3 : Delta