background image

8

System Cooling

1. Set the thermostat’s system mode to COOL and the 

fan mode to AUTO. Gradually lower the thermostat 
temperature setpoint below room temperature and 
verify the outdoor unit and indoor blower energize.

2. Verify blower wheel is spinning in direction indicated by 

arrow. Feel the air being circulated by the indoor blower 
and verify that it is cooler than ambient temperature. 
Listen for any unusual noises. If unusual sounds occur, 
determine the source of the noise and correct as 
necessary.

3. Verify HI and LO refrigerant pressures.

 

NOTE: If refrigerant pressures are abnormal and the 
compressor is rotating backwards, shut off main power to 
the unit and switch any two field wires at the disconnect. 
DO NOT alter unit wiring.

4. Allow the system to operate for several minutes and then 

set the temperature selector above room temperature. 
Verify the fan and compressor cycle off with the 
thermostat. NOTE: The blower should also stop unless 
fan switch is set to the ON position.

Table 3. LED Diagnostics for CoreSense

TM

 Diagnostics Module

ALERT CODE

ALERT CONDITION

LOCK LEVEL

LOCK INDICATION

Normal Run

Solid Yellow

Normal operation, no trip

N/A

N/A

Code1

Yellow Flash 1

Long run time. Compressor is on running for more than 18 hours.
(Code1 is disabled in Heat Pump Mode)

N/A

N/A

Code2

Yellow Flash 2

Compressor (pressure) trip. Compressor runs for 12 sec to 15 min followed 
by a compressor trip condition lasting for more than 7 min.

4x consecutive

Red: Flash2

Yellow: Off

Code3

Yellow Flash 3

Pressure switch cycling. Compressor runs for 12 sec to 15 min followed 
by a compressor trip lasting between 35 sec to 7 min.

4x consecutive

or 10x total

Red: Flash3

Yellow: Off

Code4

Yellow Flash 4

Locked rotor. Compressor trips within a compressor run time of 12 sec 
and does not start within 35 sec.

10x consecutive

Red: Flash4

Yellow: Off

Code5

Yellow Flash 5

Compressor (moderate run) trip. Compressor runs for 15 min to 18 hrs 
followed by a compressor trip lasting longer than 7 min.

4x consecutive

or 10x total

Red: Flash5

Yellow: Off

Code9

Red Flash 9

The current to the PROT terminal is greater than 2A.

Current >2A

for 40ms

Red: Flash9

Yellow: Off

Trip

Solid Red

Demand is present, but compressor is not running.

N/A

N/A

STATUS INDICATOR

STATUS TYPE

DIAGNOSTIC DESCRIPTION

C1

Operating Status

Cooling, 1st Stage

H1

Operating Status

Heating, 1st Stage

SC

Operating Status

Anti Short Cycle Timer

dF

Operating Status

Defrost

_.

Operating Status

Power on, no call for operation

01

Fault

Pressure switch, low

02

Fault

Pressure switch, high

03

Fault

Temperature Sensor, Ambient

04

Fault

Temperature Sensor, Coil

05

Fault

Board

dF

(FLASHING)

Input Error

Forced defrost - test short applied longer than 
11 minutes

Table 4. Status Indicators for Defrost Control Board

System Heating

1. Set the thermostat's system mode to HEAT and the 

temperature mode to below room temperature.

2. Verify the outdoor unit and indoor fan stop running. After 

5 minutes, increase the temperature on the thermostat 
to it's maximum setting.

3. Verify the outdoor unit and indoor blower energize. Feel 

the air being circulated by the indoor blower and verify 
that it is warmer than ambient temperature. Listen for 
any unusual noises. If unusual sounds occur, determine 
the source of the noise and correct as necessary.

Defrost Control Board Test Pins

•  Placing a jumper between the test pins for less than 1 

second will bypass the Anti-Short Cycle Timer.

•  Placing a jumper between the test pins for more than 1 

second will force the unit into a defrost cycle. As soon 
as the jumper is removed, the defrost cycle will end as 
determined by the typical criteria.

•  To determine operating status or fault conditions, refer 

to 

Table 4

 for diagnostic description.

Summary of Contents for T4BD-042 Series

Page 1: ...n how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when installing this product and using common sense plays an important role as well...

Page 2: ...orotherhazardous conditions which may result in personal injury or property damage Installation of equipment may require brazing operations Installer must comply with safety codes andwearappropriatesa...

Page 3: ...iled immediately with the carrier Pleaseconsultyourdealerformaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat P...

Page 4: ...dryer is provided with the unit and must be installedintheliquidlineofthesystem Iftheinstallation replaces a system with a filter dryer already present in the liquid line the filter dryer must be rep...

Page 5: ...y andtherestrictororifice whilebeingcarefulnottoscratch either part Carefully remove the restrictor orifice from the valve body See Figure 3 page 4 3 Check the actual size of the new orifice NOTE The...

Page 6: ...Diagnostics Module Select Models Only The CoreSenseTM Diagnostics Module Figure 5 page 7 is a breakthrough innovation for troubleshooting heatpumpandairconditioningsystemfailures Themodule installs ea...

Page 7: ...tart Check List Verify the unit is level and has sufficient clearances for unobstructed airflow Verify the outdoor coil and top of the unit are free from obstructions and debris and all equipment acce...

Page 8: ...2 sec and does not start within 35 sec 10x consecutive Red Flash4 Yellow Off Code5 Yellow Flash 5 Compressor moderate run trip Compressor runs for 15 min to 18 hrs followed by a compressor trip lastin...

Page 9: ...Data sheet for additional charging information Outdoor units with non AHRI listed indoor coils are not recommended and deviations from rated airflows or non listedcombinationsmayrequiremodificationtot...

Page 10: ...ange of operation Reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit efficiency EER or rated...

Page 11: ...below the curve T4BD 048KA Charging Chart Cooling Figure 7 Charging Chart for 4 Ton Units TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95...

Page 12: ...ring wet bulb temperatures are lower than design 1 All pressures are listed in psig and all temperatures in F 2 Discharge temperatures greater than charted values indicate an undercharged system 3 Dis...

Page 13: ...LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 121 244 135 123 245 135 267 141 125 246 135 268 141 290 147 127 247 136 269 142 291 147 313 154 129 248 136 270 142 292 148 314 154 336 160 131 271 142 293 148 31...

Page 14: ...the liquid line temperature on the inlet and outlet of the filter dryers If it is the factory dryer and in good condition there should be no temperature difference If the temperature difference is lar...

Page 15: ...0 221 232 105 45 239 250 112 60 257 268 120 75 275 286 127 90 288 299 136 105 314 325 146 121 339 350 155 31 228 239 103 46 245 256 110 61 261 272 118 76 278 289 125 91 295 306 133 106 321 332 141 122...

Page 16: ...ot suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 4...

Page 17: ...0 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air h...

Page 18: ...ts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handle...

Page 19: ...19...

Page 20: ...NO INSTALLER NAME CITY________________________ STATE_________________ Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO 7096...

Reviews: