background image

6

G R

W2

C

E

O Y

Thermostat

Green

Red

White

G

R

Black

O

Y1 IN

R

C

Air Handler

Heat  Pump 

(OD Section)

C

W

W2 OUT

W2 IN

Figure 4. Typical Thermostat  Connections

Thermostat / Low Voltage Connections

•  Thermostat connections should be made in accordance 

with the instructions supplied with the thermostat and 
the indoor equipment. A typical installation with a heat 
pump thermostat and air handler is shown in 

Figure 4

.

•  The outdoor unit is designed to operate from a 24 VAC 

Class II control circuit. The control circuit wiring must 
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having 
jurisdiction.

•  The low voltage wires must be properly connected to 

the units low voltage terminal block. Recommended 
wire gauge and wire lengths for typical thermostat 
connections are listed in 

Table 2

.

•  The  thermostat  should  be  mounted  about  5  feet 

above the floor on an inside wall. DO NOT install the 
thermostat on an outside wall or any other location 
where its operation may be adversely affected by radiant 
heat from fireplaces, sunlight, or lighting fixtures, and 
convective heat from warm air registers or electrical 
appliances. Refer to the thermostat manufacturer’s 
instruction sheet for detailed mounting and installation 
information.

CoreSense

TM

 Diagnostics Module

(Select Models Only)

The CoreSense

TM

 Diagnostics Module (

Figure 5, (page 

7)

) is a breakthrough innovation for troubleshooting 

heat pump and air conditioning system failures. The module 
installs easily in the electrical box of the outdoor unit 
near the compressor contactor.By using the compressor 
as a sensor, CoreSense Diagnostics helps the service 
technician more accurately troubleshoot system and 
compressor fault conditions.

A flashing LED indicator communicates the ALERT code 
and a diagnostic key is also imprinted on the side of the 
module to quickly direct the technician to the root cause 
of a problem.

 

Alert identification codes are also listed in 

Table 3, (page 8)

.

•  Optional equipment requiring connection to the power 

or control circuits must be wired in strict accordance 
of the NEC (ANSI/NFPA 70), applicable local codes, 
and the instructions provided with the equipment.

Grounding

 WARNING:

The unit cabinet must have an uninterrupted or 
unbroken electrical ground to minimize personal 
injury if an electrical fault should occur. Do not 
use gas piping as an electrical ground!

This unit must be electrically grounded in accordance 
with local codes or, in the absence of local codes, with 
the National Electrical Code (ANSI/NFPA 70) or the CSA 
C22.1 Electrical Code. Use the grounding lug provided in 
the control box for grounding the unit.

Table 2. Thermostat Wire

THERMOSTAT

WIRE GAUGE

MAXIMUM RECOMMENDED

THERMOSTAT WIRE LENGTH (FT)

24

25

22

45

20

70

18

110

Summary of Contents for T4BD-042 Series

Page 1: ...n how to operate and maintain the equipment for the life of the product Safety should always be the deciding factor when installing this product and using common sense plays an important role as well...

Page 2: ...orotherhazardous conditions which may result in personal injury or property damage Installation of equipment may require brazing operations Installer must comply with safety codes andwearappropriatesa...

Page 3: ...iled immediately with the carrier Pleaseconsultyourdealerformaintenanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat P...

Page 4: ...dryer is provided with the unit and must be installedintheliquidlineofthesystem Iftheinstallation replaces a system with a filter dryer already present in the liquid line the filter dryer must be rep...

Page 5: ...y andtherestrictororifice whilebeingcarefulnottoscratch either part Carefully remove the restrictor orifice from the valve body See Figure 3 page 4 3 Check the actual size of the new orifice NOTE The...

Page 6: ...Diagnostics Module Select Models Only The CoreSenseTM Diagnostics Module Figure 5 page 7 is a breakthrough innovation for troubleshooting heatpumpandairconditioningsystemfailures Themodule installs ea...

Page 7: ...tart Check List Verify the unit is level and has sufficient clearances for unobstructed airflow Verify the outdoor coil and top of the unit are free from obstructions and debris and all equipment acce...

Page 8: ...2 sec and does not start within 35 sec 10x consecutive Red Flash4 Yellow Off Code5 Yellow Flash 5 Compressor moderate run trip Compressor runs for 15 min to 18 hrs followed by a compressor trip lastin...

Page 9: ...Data sheet for additional charging information Outdoor units with non AHRI listed indoor coils are not recommended and deviations from rated airflows or non listedcombinationsmayrequiremodificationtot...

Page 10: ...ange of operation Reference the charts to determine the ideal amount of sub cooling for a given liquid pressure Units charged to other values will not perform at the rated unit efficiency EER or rated...

Page 11: ...below the curve T4BD 048KA Charging Chart Cooling Figure 7 Charging Chart for 4 Ton Units TXV Matches 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80 85 90 95...

Page 12: ...ring wet bulb temperatures are lower than design 1 All pressures are listed in psig and all temperatures in F 2 Discharge temperatures greater than charted values indicate an undercharged system 3 Dis...

Page 13: ...LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 121 244 135 123 245 135 267 141 125 246 135 268 141 290 147 127 247 136 269 142 291 147 313 154 129 248 136 270 142 292 148 314 154 336 160 131 271 142 293 148 31...

Page 14: ...the liquid line temperature on the inlet and outlet of the filter dryers If it is the factory dryer and in good condition there should be no temperature difference If the temperature difference is lar...

Page 15: ...0 221 232 105 45 239 250 112 60 257 268 120 75 275 286 127 90 288 299 136 105 314 325 146 121 339 350 155 31 228 239 103 46 245 256 110 61 261 272 118 76 278 289 125 91 295 306 133 106 321 332 141 122...

Page 16: ...ot suitable on systems that exceed 150 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 4...

Page 17: ...0 volts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air h...

Page 18: ...ts to ground 4 For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handle...

Page 19: ...19...

Page 20: ...NO INSTALLER NAME CITY________________________ STATE_________________ Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO 7096...

Reviews: