Supplementary Manual DeviceNet for NORDAC SK 200E
68
Subject to technical amendments
BU 0280 GB
7.2.2
Status word (ZSW)
The status word (ZSW) is the first word transferred to the frequency inverter in the process data section of a
response telegram.
PZD1 PZD2 PZD3 PZD4
ZSW IW1 IW2/3
IW2/3
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Meaning of the individual bits:
Bit
Value
Significance
Comments
0
0
Not on standby
1
Ready for switch-on
Initialisation complete, load relay on, output voltage disabled
1 0
Not
operational
Causes: No ON command, an error has occurred, OFF 2 or OFF 3 active, switch-
on disable status active.
1 Standby
ON command active, no errors. The inverter can be started with the ENABLE
OPERATION command.
2 0
Operation
disabled
1
Operation enabled
Output voltage enabled, run-up to present setpoint.
3 0
No
errors
1 Fault
Drive malfunctioning therefore out of order, if acknowledgement is successful, will
go to switch-on disabled status.
4
0
OFF 2
OFF 2 disable voltage command active
1
No OFF 2
5
0
OFF 3
OFF 3 rapid stop command active
1
No OFF 3
6
0
No switch-on disable
1
Switch-on disabled
Goes to standby status through OUT 1 command
7 0
No
warning
1
Warning
Drive still in operation, no acknowledgement necessary
8
0
Actual value not O.K.
Actual value does not match the setpoint (with
posicon
: Setpoint position not
reached)
1
Actual value O.K.
Actual value matches the setpoint (setpoint reached)
(with
posicon
: Setpoint position reached)
9
0
Local guidance
Local guidance active on device
1
Guidance required
The master is called upon to take over the guidance.
10 0
1
Bit 10 active
Bus bit 10 from the status word is set. For further details of function, please refer
to parameter P481.
11 0
1
Rotation right
Inverter output voltage has right-hand rotating field
12 0
1
Rotation left
Inverter output voltage has left-hand rotating field
13 0
1
Bit 13 active
Bus bit 13 from the status word is set.
For further details of function, please refer
to parameter P481.
14 0/1 Actual active
parameter set Bit 0
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15 0/1 Actual active
parameter set Bit 1