Supplementary Manual DeviceNet for NORDAC SK 200E
16
Subject to technical amendments
BU 0280 GB
2.1.2
Installation of the Customer Unit SK CU4-DEV
WARNING
Installation must be carried out by qualified personnel only, paying particular attention to
safety and warning instructions.
Modules must not be inserted or removed unless the device is free of voltage. The slots
may only be used for the applicable modules.
Installation of the SK CU4... customer unit
remote from the frequency inverter
is not
permitted. This must be installed in the immediate vicinity of the SK 200E frequency
inverter.
The installation of customer units is carried out in the connection unit SK T14
…
SK 200E underneath the
control terminal bar. Fastening is by means of the terminal bar of the frequency inverter and two M4x20 screws
(bag enclosed with the customer unit). Only one customer unit per FI is possible!
The pre-assembled cables for connection to the frequency inverter (SK 200E) are also included in the bag
enclosed with the customer unit. Connections are made according to the following table:
SK TI4-
…
with integrated customer unit SK CU4-DEV
Internal customer unit SK CU4-DEV
Bag enclosed with internal customer unit
Function
Terminal label
Cable colour
Power supply
(between frequency inverter and customer unit)
44
24V brown
40
GND blue
System bus
77
SYS+ black
78
SYS- grey
NOTE
Set the termination resistors of the system bus!
See Section 2.2.3 “Configuration”