SK 500E – Users Manual for Frequency Inverters
126
BU 0500 EN-3021
P431
Fixed frequency 3
(Fixed frequency 3)
P
-400.0 ... 400.0 Hz
{ 0.0 }
For a description of the function of the parameter, see
P429
>
Fixed frequency 1
<
Pos: 268 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P432 – Festfrequenz 4 @ 0\mod_1328000961174_388.docx @ 10158 @ @ 1
P432
Fixed frequency 4
(Fixed frequency 4)
P
-400.0 ... 400.0 Hz
{ 0.0 }
For a description of the function of the parameter, see
P429
>
Fixed frequency 1
<
Pos: 269 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P433 – Festfrequenz 5 @ 0\mod_1328001008409_388.docx @ 10181 @ @ 1
P433
Fixed frequency 5
(Fixed frequency 5)
P
-400.0 ... 400.0 Hz
{ 0.0 }
For a description of the function of the parameter, see
P429
>
Fixed frequency 1
<
Pos: 270 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P434 – Funktion Ausgang 1 (Relais 1 – MFR1) [SK 500...535E] @ 0\mod_1328001051675_388.docx @ 10204 @ @ 1
P434
Relay 1 function
(Function of output 1 (Relay 1
–
MFR1))
P
0 ... 39
{ 1 }
Control terminals 1/2:
The settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the relay
contact closes (Function 11 opens) when the limit value is reached and opens (function 11 closes)
when a 10% smaller value is undershot. This behaviour can be inverted with a negative value in
P435.
Various functions can be programmed. These can be seen in the following table.
Pos: 272 /Anleitungen/Elektronik/FU und Starter/5. Parameter/Parameterauflistung (P000 ...)/P400-P499/Parameter P434 – Liste der Funktionen der Relais- und digitalen Ausgänge @ 0\mod_1328001177097_388.docx @ 10250 @ 5 @ 1
List of possible functions of the relays and digital outputs
Value Function
Description
Signal*
00
No function
Input switched off.
Low
01
External brake
For the control of a mechanical brake on the motor. The relay switches at a
programmed absolute minimum frequency (P505). For typical brakes a setpoint
delay of 0.2 … 0.3 seconds should be programmed (see also P107).
A mechanical brake may be directly switched by AC current. (Note the technical
specification of the relay contacts!)
High
02
Inverter working
the closed relay contact indicates voltage at the inverter output (U - V - W) (also DC
run-
on(→ P559)).
High
03
Current limit
Based on the setting of the motor rated current in P203. This value can be adjusted
with the standardisation (P435).
High
04
Torque current limit
Based on motor data settings in P203 and P206. Signals a corresponding torque
load on the motor. This value can be adjusted with the standardisation (P435).
High
05
Frequency limit
Based on motor nominal frequency setting in P201. This value can be adjusted with
the standardisation (P435).
High
06
Setpoint reached
indicates that the FI has completed the frequency increase or decrease. Setpoint
frequency = actual frequency! From a difference of 1 Hz
Setpoint not reached -
contact opens.
High
07
Fault
General fault message, fault is active or not yet acknowledged.
Error: contact opens, ready: contact closes
Low
08
Warning
General warning - a limit value was reached that could lead to a later shutdown of
the FI.
Low
09
Overcurrent warning
At least 130% of the nominal FI current was supplied for 30 seconds.
Low
10
Motor overtemperature
warning
Motor overtemperature (warning): The motor temperature is evaluated via the PTC
input or a digital input.
Motor is too hot. This warning is given immediately,
overheating switch-off after 2 seconds.
Low
11
Torque current limit
active
Torque current limit/Current limit active (warning): The limiting value in P112 or P536
has been reached. A negative value in P435 inverts the reaction. Hysteresis = 10 %.
Low