Start Up and System Check
12.1
Pre-Calibration Check
1.
Before driving to a suitable setup and test location, verify system communication and
firmware versions. Follow the steps below on the ROGATOR Management Center UC5
page to locate the firmware of all components.
Turn the key switch to on to supply power to the UC5 system.
After a brief system startup, the RMC UC5 Page will display a
liability notice. Select the check button to proceed.
Select the Settings button (wrench).
Select the Next button (right arrow).
Select the Next button (right arrow).
Select the Diagnostics button (magnifying glass).
Select the Versions button (page with arrow).
Select the drop down arrow and verify that the appropriate
number of each component is shown on the list.
Select each module and check that it has the correct firmware
version.