2.1 Description of the electrical connections
0 Vac 1
0 Vac
230 Vac 2
230 Vca 50 Hz power supply
400 Vac 3
400 Vca 50 Hz power supply
Opening contactor 4
Output for OPEN contactor
Closing contactor 5
Output for CLOSE contactor
Common contactor 6
Output for COMMON contactor
Common 7
Brake or a signal light (opening limit switch)
can be connected to the terminal board no.7-8-9.
Use DIP B according to the instructions of Par. No.4.4
N.O. 8
N.C. 9
Lamp
10
Output for light or 230Vac courtesy light, maximum power for 100W lamp
11
Test
12
Isolated contact for PHOTO-TEST
13
24 Vac
14
Output 24 Vac
15
Common 16
Common contact for: services, safeties.
Photo-beam close 17
Input for photo-beam (the PHOTO will work only when closing)
Stop 18
Input for STOP
Safety Edge 19
Input for SAFETY EDGE
Pedestrian 20
Input for PARTIAL OPENING
Start 21
Input for START control
Common 22
Common contact for: services, safeties
Common 23
Common contact for: services, safeties
Common 24
Common contact for: services, safeties, coaxial antenna cable
Antenna 25
+ Antenna
OLS 26
Input for OPENING limit switch
CLS 27
Input for CLOSING limit switch
Open 28
Input for OPEN
Close 29
Input for CLOSE
Isolated contact 30
Isolated contact for light
Isolated contact 31
Isolated contact for light
man present OPEN 32
Contact for “man present” OPEN
man present CLOSE 33
Contact for “man present” CLOSE
Common 34
Common
2
Installation of the control unit
START-S5PV
Technical manual