Management
Overview
Management Overview includes a comprehensive menu structure for all installation options. Therefore, there will be features in the document that
does not appear on the stated facilities. Subsequently indexes relate to:
Temperature
1
Temperature information and settings
Summer / winter T (°C)
12.0
°C 2 Outdoor temperature for sum-
mer/winter mode change
Sum / win T offset (°C)
2.0
°C 2 Summer/winter mode change offset
Night setback temp (°C)
3.0
°C 2 Night setback temperature
CompactP
Air (°C)
20.0
°C 1 Temperature setpoint
Hot water (°C)
45.0
°C 1 Setpoint for domestic hot-water
Minimum winter T7 (°C)
16.0
°C 2 Lowest allowable supply air tempera-
ture in winter
Minimum summer T7 (°C)
5.0
°C 2 Lowest allowable supply air tempera-
ture in summer
Maximum T7 (°C)
50.0
°C 2 Maximum allowable supply air temper-
ature
Master sensor
T3 / T7 /
TPanel / T18
2 Set controlling sensor for the system
Regulate deadband (°C)
1
°C 2 Temperature regulation dead band for
master sensor
Bypass damper offs.(°C)
1.0
°C 2 Setpoint offset for bypass damper
1:
User
2:
Super User
3:
Installer
4:
Administrator