Superuser/ Installer – Settings
*** AllowHeat deadband (°C) - Used to control external heating system
Permits external heating system to run when:
Room temperature (T3) < Temp. s/- ”Ext. heating neutral zone” – 1 °C
Blocks external heating system when:
Room temperature (T3) > Temp. s/- ”Ext. heating neutral zone”
E.g.
CP –
Settings
(continue)
Legionella funkt.*
Legionella - Off
No automatic legionella combat system
Legionella - Weekly
Legionella combat system runs once a week
Legionella - Monthly
Legionella combat system runs once a month
Start legionella now
You can start legionella combat system manually
Day for anti-legionella
Weekday or month in which legionella combat system will
run
Legionella start (h)
Time of day at which legionella combat system will start
SHW
SHW minumum temp.
(°C)
Minimum temperature in hot water tank T11
SHW max. temp. (°C)
Maximum temperature in hot water tank T12
SHW heater enable
Switch electrical supplementary domestic hot water ON or
OFF
Supply /
Extract air
Outdoor air filter
You can select filter control here.
Days from filter change
How long since last filter change?
Days between filter chg
Set no. of days between filter changes
Sup. filt. timer reset
Activate after filter change and reset no. of days from last
filter change
*Heat domestic hot water to 65 °C in 5 minutes.
Ext. heating neutral zone - 3°C
20 °C
- 1 °C
< 16 °C external heating released
> 17 °C external heating blocked