4.2.1 Functions of Control Circuit Terminals
Standard configuration of control circuit terminals
Type
Termina
Terminal function
Technical specification
Digital
input
X1
~
X3
Multi-functional input
terminals 1
~
3
Optical-isolator input
Frequency range:
:
0
~
200Hz
Voltage range: 0
~
24V
X4
X5
Multi-functional input or
Single pulse input 4, 5
Multi-functional input
:
same as
X1
~
X3
Single Pulse input:
:
0.1Hz
~
50kHz
Voltage range
:
0
~
24V
COM
multi-functional input
terminals common end
Internal isolated with GND
Digital
output
24V
24V
24V±5%, Maximum load :200mA,
with overload and short circuit
protection
Y1
Open collector output 1
Optical-isolator output
maximum output current: 50mA
Output voltage range
:
0
~
24V
DO
Open collector or high
speed pulse output
Output frequency: 0
~
50kHz
Open collector same as Y1
COM
Open collector output
common end
Internal isolated with GND
Analog
input
10V
Analog input reference
voltage
Open circuit voltage up to 11V;
Internal isolated with com;
Maximum load 30mA
,
with
overload and short circuit
protection
AI1
Analog input channel 1
Input Voltage range
:
0
~
10V
Input impedance
:
100kΩ
AI2
Analog input channel 2
Input Voltage range
:
0
~
10V
Input impedance
:
100kΩ
Input current range
:
0
~
30mA
Current Input impedance
:
500Ω,
0~20mA or 0~10V analog input
can be selected through DIP