NE200&300 Quick Start Guide
51
Code
Description
Setting range
Default
Modify
Modbus
Address
F8.02
Analog PID
digital setup
0.0
~
999.9
50
○
0902H
F8.03
Analog closed
loop measuring
range
1.0
~
999.9
100
○
0903H
F8.04
PID action
direction
0: Positive
1: Negative
0
○
0904H
F8.05
PID proportional
gain 1 (KP1)
0.1
~
9.9
1
○
0905H
F8.06
PID integration
time 1
0
~
100s
10s
②
3s
③
○
0906H
F8.07
PID differential
time 1
0.00
~
1.00s
0.00s
○
0907H
F8.08
PID proportional
gain 2 (KP2)
0.1
~
9.9
1
○
0908H
F8.09
PID integration
time 2
0.0
~
100.0s
10.0s
○
0909H
F8.10
PID differential
time 2
0.00
~
1.00s
0.00s
○
090AH
F8.11
PID parameters
switching
0: No switching, use
the first group
parameters
0
○
090BH
1: switching by
terminal
2: auto-switching by
deviation
F8.12
PID parameter
switching
Deviation 1
0.0
~
999.9
20
○
090CH
F8.13
PID parameter
switching
Deviation 2
0.0
~
999.9
80
○
090DH
F8.14
PID delay time
constant
0.0
~
100.0s
0.0s
○
090EH
F8.15 Deviation limit
0.0
~
999.9
0.2
○
090FH