NE200&300 Quick Start Guide
32
Code
Description
Setting range
Default
Modify
Modbus
Address
proportional gain 2
F3.04
Speed loop integral
time 2
1~3000
200
○
0404H
F3.05
Switching
frequency 2
0.0
~
60.00Hz
10.00Hz
○
0405H
F3.06
Speed loop filter
time constant
0
~
500ms
2ms
②
3ms
③
○
0406H
F3.07
Current loop
proportional
coefficient
0
~
6000
3000
○
0407H
F3.08
Current loop
integral coefficient
0
~
6000
1500
○
0408H
F3.09
VC Slip
compensation
0.0
~
200.0%
100.00%
○
0409H
F3.10
②
Torque control
0:Torque control
Disabled
0
○
040AH
1:Torque digital
setting(F3.11)
2:AI1 3:AI2
4:Reserved
5:communication
6:keypad
potentiometer
③
Torque control
0:Torque control
Disabled
1:Torque digital
setting(F3.11)
2:AI1 3:AI2
4:Pulse
5:communication
6:keypad
potentiometer
0
○
040AH
F3.11
Torque digital
setting
0.0
~
200.0%
50.00%
○
040BH
F3.12 Torque control
0: digital
0
○
040CH