22
CONNECTIONS
POWERDRIVE MD2CS Installation guide
4946 - 2017.12 / c
en
3.1.4 - Cables and fuses
• It is the responsibility of the user to connect and provide protection for the POWERDRIVE MD2CS in accordance
with the current legislation and regulations in the country of use. This is particularly important with regard to the
size of the cables, the type and rating of fuses, the earth or ground connection, powering down, acknowledging trips,
isolation and protection against overcurrents.
• The installation must have a short circuit current (Isc) > 20 I
L
at the point of drive connection.
• This table is given for information only, and must under no circumstances be used in place of the current standards.
I
L
:
Maximum line current
Ico:
Continuous output current
POWERDRIVE
rating
AC supply
Motor
400 V - 50 Hz
460/480 V - 60 Hz
I
L
(A)
Fuses (1)
Cable
cross-
section
(mm²)
(2) (4)
I
L
(A)
Fuses (1)
Cable cross-
section (mm²)
(2) (4)
Ico
(A)
Cable
cross-
section
(mm²)
(3) (4)
Gg
type
aR type
(IEC
&UL)
Gg
type
aR
type
Class
J
(UL)
60T
Heavy
85
100
160
3x35 + PE
75
100
125
125
3x35 + PE
92
3x35 + PE
Normal
105
125
200
3x35 + PE
90
125
160
150
3x35 + PE
112
3x35 + PE
75T
Heavy
105
125
200
3x35 + PE
90
125
160
150
3x35 + PE
118
3x35 + PE
Normal
140
160
250
3x50 + PE
120
160
200
200
3x35 + PE
142
3x50 + PE
100T
Heavy
140
160
250
3x50 + PE
120
160
250
200
3x50 + PE
142
3x50 + PE
Normal
170
200
315
3x70 + PE
150
200
250
225
3x70 + PE
175
3x70 + PE
120T
Heavy
170
200
315
3x70 + PE
150
200
250
225
3x70 + PE
170
3x70 + PE
Normal
205
250
350
3x95 + PE
180
200
315
250
3x70 + PE
212
3x95 + PE
150T
Heavy
205
250
400
3x95 + PE
180
200
315
250
3x70 + PE
220
3x95 + PE
Normal
245
315
450
3x120 + PE
210
250
350
300
3x95 + PE
250
3x120 + PE
180T
Heavy
245
315
500
3x120 + PE
210
250
400
300
3x95 + PE
260
3x150 + PE
Normal
295
315
500
3x150 + PE
240
315
450
400
3x120 + PE
315
3x185 + PE
220T
Heavy
295
315
550
3x150 + PE
240
315
450
400
3x120 + PE
310
3x185 + PE
Normal
370
400
630
3x240 + PE
360
400
550
500
3x240 + PE
400
3x240 + PE
270T
Heavy
370
400
700
3x240 + PE
360
400
700
500
3x240 + PE
375
3x240 + PE
Normal
460
500
800
2x[3x150 + PE]
420
500
800
600
2x[3x120 + PE]
470
2x[3x150 + PE]
340T
Heavy
460
500
800
2x[3x150 + PE]
420
500
800
600
2x[3x120 + PE]
470
2x[3x150 + PE]
Normal
580
630
1000
2x[3x185 + PE]
535
630
1000
--
2x[3x185 + PE]
580
2x[3x185 + PE]
400T
Heavy
580
630
1000
2x[3x185 + PE]
535
630
1000
--
2x[3x185 + PE]
540
2x[3x185 + PE]
Normal
650
800
1100
2x[3x240 + PE]
595
630
1000
--
2x[3x185 + PE]
650
2x[3x240 + PE]
470T
Heavy
650
800
1250
2x[3x240 + PE]
595
630
1000
--
2x[3x185 + PE]
670
2x[3x240 + PE]
Normal
825
1000
1400
4x[3x120 + PE]
710
800
1250
--
4x[3x95 + PE]
800
4x[3x120 + PE]
570T
Heavy
735
1000
1400
4x[3x120 + PE]
710
800
1250
4x[3x95 + PE]
750
4x[3x120 + PE]
Normal
915
1000
1600
4x[3x150 + PE]
770
1000
1400
4x[3x120 + PE]
880
4x[3x150 + PE]