8
GENERAL INFORMATION
POWERDRIVE MD2CS Installation guide
4946 - 2017.12 / c
en
1.4 - Electrical characteristics
All work relating to installation, commissioning and maintenance must be carried out by experienced, qualified
personnel.
1.4.1 - General characteristics
Characteristic
Level
Power supply voltage
3-phase mains supply: 400 V -10% to 480 V +10% ("T" ratings) or
525 V -10% to 690 V +10% ("TH" ratings)
Phase voltage imbalance
< 2%
Input frequency
«T» ratings: 50 or 60 Hz ± 5%
«TH» ratings: 50 Hz ± 5%
Maximum number of power-ups per hour (power)
20
Output frequency range
0 to 590 Hz
Forced ventilation and auxiliary power supply power and voltage refer to §3.13.1.1
ROHS conformance
Conforming to standard 2002-95-EC
1.4.1 - Electrical characteristics
Ico
: Continuous output current.
Pout
: Output power.
Imax (60s)
: Maximum output current, available for 60 seconds every 600 seconds.
Heavy duty
: For heavy-duty constant torque machines (presses, grinders, hoisting, etc) and all applications where significant
inertia has to be accelerated quickly (centrifuges, translation of travelling cranes, etc).
Normal duty
: For normal-duty constant torque or centrifugal torque machines (fans, compressors, etc).
CAUTION: In its factory setting, the drive operates with a switching frequency of 3 kHz.
400 V to 460 V 3-phase supply
Switching frequency = 3 kHz - ambient temperature ≤ 40°C - altitude ≤ 1,000 m.
Rating
Heavy duty
Normal duty
Imax (60 s)
(A)
Pout at 400 V
(kW)
(1)
Pout at 460 V
(HP)
(1)
Ico
(A)
Pout at 400 V
(kW)
(1)
Pout at 460 V
(HP)
(1)
Ico
(A)
60T
45
60
92
55
75
112
130
75T
55
75
118
75
100
142
165
100T
75
100
142
90
125
175
200
120T
90
125
170
110
150
212
240
150T
110
150
220
132
175
250
312
180T
132
175
260
160
200
315
365
220T
160
200
310
200
300
400
435
270T
200
300
375
250
350
470
530
340T
250
350
470
315
450
580
660
400T
315
450
540
355
500
650
760
470T
355
500
670
450
600
800
940
570T
400
600
750
500
650
880
1050
(1) Motor winding voltage