Considerable drop in voltage, on-load
Check the generator
load level
Check the quadrature
droop parameter settings
Check the wiring of the
voltage reference U/V/W
Check the position and
location of the CT on
phase U
Decrease the load
Check the value of the
CT and the ratio setting
Modify PID parameters
of the D510C
Start generator and
control running
Adjust the quadrature
droop
(factory setting 3%)
Modify the wiring
Modify the wiring
Check the D500
configuration
(LAM, U/F, etc)